Line 22: Line 22:  
[[File:Modbusupdategateway1.png|1000px|border|class=tlt-border]]
 
[[File:Modbusupdategateway1.png|1000px|border|class=tlt-border]]
   −
* In the configuration section, press '''Enable''' to enable the serial interface
+
A new window will open, where the device should be configured according to these steps:
* In the Serial '''Type''' section, select '''Modbus gateway'''. ////editable
  −
You may need to change configuration depending on your needs, just make sure that identical settings are set here and in RTU simulator: Baud rate, data bits, parity, stop bits, flow control
  −
 
  −
[[File:Navigateandenable.png|border|class=tlt-border]]
  −
 
  −
This will expand more customization options:
      +
* Press '''Enable''' to enable the serial interface
 
* '''Listening IP''' – IP interface on which you are listening for incoming connections (input 0.0.0.0 to listen on any IP address)
 
* '''Listening IP''' – IP interface on which you are listening for incoming connections (input 0.0.0.0 to listen on any IP address)
 
* '''Port''' – Port number for Modbus gateway (default port is 502)
 
* '''Port''' – Port number for Modbus gateway (default port is 502)
 
* '''Slave ID''' configuration type – User defined or obtained from TCP
 
* '''Slave ID''' configuration type – User defined or obtained from TCP
 
* '''Slave ID''' – preconfigured Slave ID number
 
* '''Slave ID''' – preconfigured Slave ID number
 +
 +
You may need to change configuration depending on your needs, just make sure that identical settings are set here and in RTU simulator: Baud rate, data bits, parity, stop bits, flow control
 +
 +
[[File:Navigateandenable.png|border|class=tlt-border]]
    
[[File:Moreconfigurationoptions.png|border|class=tlt-border]]
 
[[File:Moreconfigurationoptions.png|border|class=tlt-border]]
   −
In IP filter options on the serial configuration page, add IP addresses that will be allowed to reach your Modbus gateway (input 0.0.0.0/0 to allow any IP address).
+
In IP filter options on the bottom of the page, add IP addresses that will be allowed to reach your Modbus gateway (input 0.0.0.0/0 to allow any IP address).
    
[[File:Ipfilter1.png|border|class=tlt-border]]
 
[[File:Ipfilter1.png|border|class=tlt-border]]