Line 1: |
Line 1: |
− | {{Template: Networking_rutos_manual_fw_disclosure | + | {{Template: Networking_device_manual_fw_disclosure |
− | | fw_version ={{Template: Networking_rutos_manual_latest_fw | + | | series = {{{series}}} |
| + | | name = {{{name}}} |
| + | | fw_version ={{Template: Networking_device_manual_latest_fw |
| | series = {{{series}}} | | | series = {{{series}}} |
| | name = {{{name}}} | | | name = {{{name}}} |
Line 14: |
Line 16: |
| This manual page provides an overview of the BACnet functionality in {{{name}}} devices. | | This manual page provides an overview of the BACnet functionality in {{{name}}} devices. |
| | | |
− | <b>Note:</b> BACnet is additional software that can be installed from the <b>Services → [[{{{name}}} Package Manager|Package Manager]]</b> page.</u> | + | <b>Note:</b> BACnet is additional software that can be installed from the <b>System → [[{{{name}}} Package Manager|Package Manager]]</b> page.</u> |
| | | |
| ==General Configuration== | | ==General Configuration== |
Line 42: |
Line 44: |
| </tr> | | </tr> |
| <tr> | | <tr> |
− | <td>Port forward</td> | + | <td>Allow Remote Access</td> |
| <td>off | on; default: <b>off</b></td> | | <td>off | on; default: <b>off</b></td> |
| <td>Creates port forward firewall rule to make application port in LAN reachable from selected BBMD interface.</td> | | <td>Creates port forward firewall rule to make application port in LAN reachable from selected BBMD interface.</td> |
Line 58: |
Line 60: |
| <tr> | | <tr> |
| <td>Gateway port</td> | | <td>Gateway port</td> |
− | <td>integer [0..65535]; default: <b>none</b></td> | + | <td>integer [1..65535]; default: <b>none</b></td> |
| <td>Gateway port number.</td> | | <td>Gateway port number.</td> |
| </tr> | | </tr> |
Line 77: |
Line 79: |
| <tr> | | <tr> |
| <td>BIP port</td> | | <td>BIP port</td> |
− | <td>integer [0..65535]; default: <b>47808</b></td> | + | <td>integer [1..65535]; default: <b>47808</b></td> |
| <td>BIP UDP port.</td> | | <td>BIP UDP port.</td> |
| </tr> | | </tr> |
Line 84: |
Line 86: |
| ==MSTP Configuration== | | ==MSTP Configuration== |
| | | |
− | Master - Slave Token Passing (<b>MSTP</b>) is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 31 devices to be installed on a single network.
| + | <b>MSTP</b> is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 31 devices to be installed on a single network. |
| | | |
| [[File:Networking_rutos_manual_bacnet_mstp_configuration_v2.png|border|class=tlt-border]] | | [[File:Networking_rutos_manual_bacnet_mstp_configuration_v2.png|border|class=tlt-border]] |
Line 101: |
Line 103: |
| <tr> | | <tr> |
| <td>MSTP MAC max</td> | | <td>MSTP MAC max</td> |
− | <td>integer [0..127]; default: <b>127</b></td> | + | <td>integer [1..127]; default: <b>127</b></td> |
− | <td>Maximum master address in the MSTP network.</td> | + | <td>Maximum client address in the MSTP network.</td> |
| </tr> | | </tr> |
| <tr> | | <tr> |
| <td>Baud rate</td> | | <td>Baud rate</td> |
− | <td>300 {{!}} 1200 {{!}} 2400 {{!}} 4800 {{!}} 9600 {{!}} 19200 {{!}} 38400 {{!}} 57600 {{!}} 115200 {{!}} 230400 {{!}} 460800 {{!}} 921600 {{!}} 1000000 {{!}} 3000000; default: <b>38400</b></td> | + | <td>300 {{!}} 600 {{!}} 1200 {{!}} 2400 {{!}} 4800 {{!}} 9600 {{!}} 19200 {{!}} 38400 {{!}} 57600 {{!}} 115200 {{!}} 230400{{#switch:{{{series}}}|RUT9|TRB2|TRB1|TRB2M= {{!}} 460800 {{!}} 921600 {{!}} 1000000 {{!}} 3000000}}; default: <b>38400</b></td> |
| <td>Serial data transmission rate (in bits per second).</td> | | <td>Serial data transmission rate (in bits per second).</td> |
| </tr> | | </tr> |
| <tr> | | <tr> |
| <td>Parity</td> | | <td>Parity</td> |
− | <td>Even {{!}} Odd{{#switch:{{{series}}}|TRB2|TRB1= {{!}} Mark {{!}} Space}} {{!}} None; default: <b>None</b></td> | + | <td>Even {{!}} Odd {{!}} Mark {{!}} Space {{!}} None; default: <b>None</b></td> |
| <td>In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check. | | <td>In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check. |
| <ul> | | <ul> |
| <li><b>None</b> (<b>N</b>) - no parity method is used.</li> | | <li><b>None</b> (<b>N</b>) - no parity method is used.</li> |
| <li><b>Odd</b> (<b>O</b>) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.</li> | | <li><b>Odd</b> (<b>O</b>) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.</li> |
− | <li><b>Even</b> (<b>E</b>) - the parity bit is set so that the number of "logical ones (1s)" has to be even.</li>{{#switch:{{{series}}}|TRB2|TRB1=<li><b>Space</b> (<b>S</b>) - the parity bit will always be a binary 0.</li> | + | <li><b>Even</b> (<b>E</b>) - the parity bit is set so that the number of "logical ones (1s)" has to be even.</li> |
− | <li><b>Mark</b> (<b>M</b>) - the parity bit will always be a binary 1.</li>}} | + | <li><b>Space</b> (<b>S</b>) - the parity bit will always be a binary 0.</li> |
| + | <li><b>Mark</b> (<b>M</b>) - the parity bit will always be a binary 1.</li> |
| </ul> | | </ul> |
| </td> | | </td> |
Line 123: |
Line 126: |
| <tr> | | <tr> |
| <td>Data bits</td> | | <td>Data bits</td> |
− | <td>{{#switch:{{{series}}}|TRB2|TRB1=7 {{!}} 8|#default=8}}; default: <b>8</b></td> | + | <td>{{#switch:{{{series}}}|TRB2|TRB2M=7 {{!}} 8|RUT9=8|#default=5 {{!}} 6 {{!}} 7 {{!}} 8}}; default: <b>8</b></td> |
| <td>Number of data bits for each character.</td> | | <td>Number of data bits for each character.</td> |
| </tr> | | </tr> |
| <tr> | | <tr> |
| <td>Stop bits</td> | | <td>Stop bits</td> |
− | <td>1{{#switch:{{{series}}}|TRB2|TRB1= {{!}} 2}}; default: <b>1</b></td> | + | <td>1 {{!}} 2; default: <b>1</b></td> |
− | <td>Stop bits sent at the en of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used..</td> | + | <td>Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used..</td> |
| </tr> | | </tr> |
| </table> | | </table> |
| | | |
| [[Category:{{{name}}} Services section]] | | [[Category:{{{name}}} Services section]] |