RUT300 Data to Server: Difference between revisions

From Teltonika Networks Wiki
No edit summary
No edit summary
 
(One intermediate revision by the same user not shown)
Line 7: Line 7:
| wifi      = 0
| wifi      = 0
| mobile    = 0
| mobile    = 0
| mobile_usage = 1
| MNF = 1
| MQTT = 1
| DLMS = 1
| DNP3 = 1
| Modbus = 1
| OPC = 1
}}
}}

Latest revision as of 15:25, 25 June 2024

Main Page > EOL Products > RUT300 > RUT300 Manual > RUT300 WebUI > RUT300 Services section > RUT300 Data to Server

The information in this page is updated in accordance with firmware version RUT30X_R_00.07.11.


Summary

The Data to Server feature provides you with the possibility to set up data senders that collect data from various sources and periodically send it to remote servers.


If you're having trouble finding this page or some of the parameters described here on your device's WebUI, you should turn on "Advanced WebUI" mode. You can do that by clicking the "Advanced" button, located at the top of the WebUI.

Data Senders

A Data Sender is an instance that gathers and periodically sends collected data to a specified server. The Data Senders list is empty by default so, in order to begin configuration you must add a new collection first. To add a new collection, click the 'Add' button.

After this you should be redirected to the newly added data configuration page.

Data configuration


Refer to the table below for descriptions on data configuration fields.

Note: these tables have coloring schemes to indicate which fields can be seen with different configuration.

Field Value Description
Name string; default: input1 Name of data input.
Type Base | Lua script | Mobile usage| MNF info | Modbus* | Modbus Alarms | DNP3* | MQTT | OPC UA* | DLMS*; default: Base Data input type.
Format type Json | Custom | Lua script; default: Json Arranges the format of the sent JSON segment.
Values list; default: All values included Select values based on the data input type. If no values are selected, all values will be included.
Format string string; default: none Specifies custom format string.
Empty value string; default: N/A A string which will be placed if any value cannot be received.
Delimeter string (Maximum length of value is 1 bytes); default: N/A Specifies delimiters for multiple data segments.
Lua format example script -(interactive button) Download the Lua script.
Lua format script -(interactive button) Upload the Lua script.
Segment count integer [1..64]; default: 1 Max segment count in one JSON string sent to server.
Send as object off | on; default: off When turned on, sends JSON segment as object and not as an array element.
Data filtering All | Server ID | Alarm ID | Register number; default: All If Data type: Modbus alarms data. Choose which data this sender will send to server.
Data filtering All | Server IP address | Server ID | Request name ; default: All If Data type: Modbus data. Choose which data this sender will send to server.
Lua data example script -(interactive button) Download Lua data example script.
Lua script -(interactive button) Upload Lua data script.
Data filtering All | Name; default: All If Data type: DLMS. Choose which data this sender will send to server.
Invert file off | on; default: off If Data type: DLMS. Inverts filter condition.
Data filtering All | Address | IP; default: All If Data type: DNP3. Choose which data this sender will send to server.
Database RAM | Flash; default: RAM Database location
Data filtering All | Name ; default: All If Data type: OPC UA. Choose which data this sender will send to server.
Server address Default: empty Hostname or ip address of the broker to connect to.
Port integer [0..65535]; default: 1883 Port number for connecting to MQTT.
Keepalive integer [1..640]; default: 60 MQTT Keepalive period in seconds.
Topic string; default: none MQTT topic to be used for publishing the data.
Client ID string; default: none Client ID to send with the data. If empty, a random client ID will be generated
QoS integer [0..2]; default: 0 MQTT Quality of Service. Allowed values:
  • 0 - when we prefer that the message will not arrive at all rather than arrive twice,
  • 1 - when we want the message to arrive at least once but don't care if it arrives twice (or more),
  • 2 - when we want the message to arrive exactly once. A higher QoS value means a slower transfer.
Enable secure connection off | on; default: off Enables the use of TLS certificates.
On: TLS type Certificate based | Pre-shared key based; default: Certificate based Select type of TLS.
Certificate based: Allow insecure connection off | on; default: off Allow not verifying server authentication.
Certificate based: Certificate files from device off | on; default: off Specify where the certificates will be used from.
Certificate based: CA File .ca file; default: none Certificate authority is an entity that issues digital certificates. A digital certificate certifies the ownership of a public key by the named subject of the certificate.
Certificate based: Client certificate .crt file; default: none Certificate file is a type of digital certificate that is used by client systems to make authenticated requests to a remote server. If client certificate is not needed, leave both client certificate and client key fields empty.
Certificate based: CLient private Key .key file; default: none File containing private key for this client. This file needs to be not encrypted.
Pre-shared key based: Pre-Shared-Key string; default: none The pre-shared-key in hex format with no leading "0x".
Pre-shared key based: Identity string; default: none The identity of this client. May be used as the username depending on the server settings.
Username string; default: none Username used in authentication.
Require password on | off; default: off Enables password for authentication.
Password string; default: none Password used in authentication.


* This is additional software that can be installed from the System → Package Manager page.

Collection configuration


> > > > > >
Field Value Description
Enabled off | on; default: on Enables data to server collection instance.
Timer Period | Scheduler | None; default: Period Strategy for collecting/sending data to destination.
Period integer; default: 60Interval in seconds for collecting/sending data to destination.
Day time string; default: noneDay time when action should be executed. Use '*' to indicate every hour or minute, (e.g., 12:15, *:15, 12:*, or *:*).
Interval type Weekdays | Month days; default: WeekdaysAllows selecting between week and month days for instance intervals.
Weekdays list; default: Every day is selectedWeekdays, when data should be sent/collected. If nothing is selected, every day of the week will be included.
Month day list; default: Every day is selectedMonth days, when data should be sent/collected. If nothing is selected, every day of the month will be included.
Month day: Force last day off | on; default: offForces intervals to accept last day of month as valid option if selected day doesn't exist in ongoing month.
Retry off | on; default: off In case of a failed attempt, retry to send the same data to destination later.
Retry count Default: 10 Retry to send the same data N times
Timeout Default: 1 Timeout in second between retry attempts
Format type JSON | custom | Lua script; default: JSON Data collection objects formatting.
Format string Default: Instance name Specifies custom format string
Empty value Default: N/A A string which will be placed if any value cannot be received
Lua format example script -(interactive button) Download the Lua script.
Lua format script -(interactive button) Upload the Lua script.

Server configuration


Field Value Description
Type HTTP | MQTT; default: HTTP Interval in seconds for collecting/sending data to destination.
Server address Default: empty Hostname or IP address of the broker to connect to.
HTTP headers Default: empty Allows to add custom headers to the HTTP requests.
Enable secure connection off | on; default: off Enables the use of TLS certificates.
Port integer [0..65535]; default: 1883 Port number for connecting to MQTT.
Keepalive integer [1..640]; default: 60 MQTT Keepalive period in seconds.
Topic string; default: none MQTT topic to be used for publishing the data.
Client ID string; default: none Client ID to send with the data. If empty, a random client ID will be generated
QoS integer [0..2]; default: 0 MQTT Quality of Service. Allowed values:
  • 0 - when we prefer that the message will not arrive at all rather than arrive twice,
  • 1 - when we want the message to arrive at least once but don't care if it arrives twice (or more),
  • 2 - when we want the message to arrive exactly once. A higher QoS value means a slower transfer.
Allow insecure connection off | on; default: off Allow not verifying server authentication.
Certificate files from device off | on; default: off Specify where the certificates will be used from.
Certificate authority file .ca file; default: none Certificate authority is an entity that issues digital certificates. A digital certificate certifies the ownership of a public key by the named subject of the certificate.
Client Certificate .crt file; default: none Certificate file is a type of digital certificate that is used by client systems to make authenticated requests to a remote server. If client certificate is not needed, leave both client certificate and client key fields empty.
Client Private Keyfile .key file; default: none File containing private key for this client. This file needs to be not encrypted.
Use credentials off | on; default: off Enables use of username and password for authentication.
On: Username string; default: none Username used in authentication.