Template:RutOS configuration example MQTT Gateway Demo LV: Difference between revisions

From Teltonika Networks Wiki
Line 19: Line 19:
#Enter device ID
#Enter device ID
#Press '''Save & Apply'''
#Press '''Save & Apply'''
[[File:Networking MQTT MODBUS flespi configuration.png|center]]
[[File:Networking MQTT MODBUS flespi configuration.png|border|class=tlt-border]]


''*In this configuration LAN port is used hence “Allow Remote Access” is not needed''
''*In this configuration LAN port is used hence “Allow Remote Access” is not needed''

Revision as of 13:32, 26 August 2024

Summary

In this guide, Modbus TCP master MQTT Gateway function will be configured with two different types of MQTT Brokers. First using third-party MQTT Broker services (in this example Flespi.io). Second, using the RUT240 router as MQTT Broker. Two {{{name}}} routers will be used as Modbus TCP Master and Slave, and the PC acts as MQTT Publisher and Subscriber.

Configuration overview & prerequisites

  • Two {{{name}}} routers - one acts as Modbus TCP Master (Client), another as Modbus TCP Slave (Server)
  • Flespi.io account to act as an MQTT Broker/Publisher/Subscriber (for first configuration example)
  • RUT240 with a Public IP address to act as MQTT Broker (for second configuration example)
  • An end device (PC, Laptop) to act as MQTT Subscriber/Publisher (for second configuration example)

Configuration using flespi.io as MQTT Broker

Configuring {{{name}}} Modbus TCP Server


Go to Services → Modbus → Modbus TCP Server:

  1. Check Enable
  2. Enter port that will be used, in this example 502 will be used
  3. Enter device ID
  4. Press Save & Apply

*In this configuration LAN port is used hence “Allow Remote Access” is not needed

Modbus TCP Server {{{name}}} is now configured.

Configuring {{{name}}} Modbus TCP Master


Go to Services → Modbus → Modbus TCP Master

  1. Press Add
  2. Check Enable
  3. Enter the name for the slave device
  4. Slave ID must match with the previously configured Slave device ID
  5. Enter the IP address of the Modbus TCP Slave device
  6. Chose same Port as in Slave device - 502
  7. Enter Period in seconds, how often requests will be sent to the Slave device
  8. Enter new request name and press Add in Requests configurations
  9. Choose Data type and Function, enter First register/coil/input to be read or written and Register count. You can name each individual configuration, and then select enable on configurations that you want to use. In this example, register to get Routers name is used.
  10. Press the Test button in Request Configuration Testing to see if the Slave device responds to requests, a response similar to the image below should be shown.
  11. Press Save & Apply

List of available Modbus parameters can be found here

Configuring Flespi.io MQTT Broker


  1. Log in or create an account on https://flespi.io

Once logged in:

  1. Navigate to MQTT Board on the left side of the screen and press it.
  2. On the right-hand panel, top right corner, next to the name of the MQTT board, press the cogwheel-looking icon to open Connection Settings
  3. In the opened window, press "Get flespi token" to generate a username
  4. Enter Client name
  5. Copy Host address
  6. Copy Username
  7. Create a password
  8. Press Save

Configuring MQTT Gateway on {{{name}}} Modbus TCP Master


Open routers WebUI and navigate to Services → Modbus → MQTT Gateway

  1. Select Enable
  2. Enter Host (copied from flespi connection settings without 'wss://' and port)
  3. Enter Username (Copied from flespi Connection settings generated token)
  4. Enter Password

You can change Request and Response topics that you will have to publish and subscribe to get information from Modbus TCP Master through MQTT Gateway, but for this example, they are left on default topics

Message format for MQTT publisher


The format is in the text - heavier and slower, but less difficult to edit.

1. Format version 0
2. Cookie from 0 to 264 -1
3. IP Type 0 - IPv4; 1 - IPv6; 2 - hostname
4. IP IPv6 must be in full format (for example: 2001:0db8:0000:0000:0000:8a2e:0370:7334)
5. Port Port number (for example: 502)
6. Timeout in seconds (time to wait for response) from 1 to 999
7. Slave ID - Indicates to which slave request is sent from 1 to 255
8. Function 3 - read registers; 6 - write single register; 16 - write multiple registers
9. Number of the first register from which information will be read or written from 1 to 65535
10. Registry value If function is 3 - from 1 to 123 (first register + registry value can not go out of range);

If function is 6 - from 0 to 65535

If function is 16 - from 1 to 123 (first register + registry value can not go out of range), Registry values separated by commas without spaces. Example.: 1,2,3,654,21,789. There has to be as many values, as specified number of registers, and each value must be between 0 and 65535. If number of registries is 0, there should be no registry values

Examples


Setting relay (on) (Relay address is 202, which means 'Number of first register will be 203) 0 65432 0 192.168.1.1 502 5 1 6 203 1
Getting uptime 0 65432 0 192.168.1.1 502 5 1 3 2 2

Testing MQTT Publisher and Subscriber on flespi.io


Log in and navigate to MQTT Board on https://flespi.io

Add a Subscriber:

  1. Press '+' button on the top right corner
  2. Select 'Subscriber'
  3. In the topic field enter 'response'
  4. Press 'Subscribe' button

Add a Publisher:

  1. Press '+' button on the top right corner
  2. Select 'Publisher'
  3. In the topic field enter 'request'
  4. In the message field enter message, for this example 'Getting uptime' is used
  5. Press 'Publish' button


Check the response in the 'Subscriber' tab, you should receive a message similar to the one below.


When the value climbs over 65535 the counter resets and the value held by the first register increases by 1. So one way to interpret the results would be to multiply the value in the first register by 216 and add it to the value of the second register. In this example: 9 * 65536 + 3502 = 593326s or 6 days 20 hours 48 minutes and 46 seconds.

This Means that MQTT Gateway on Modbus TCP Master router is working correctly and Modbus TCP Slave receives requests.

Configuration using RUT240 router as MQTT Broker

[[File:{{{name}}}_mqtt_broker_configuration_scheme_2.png|987x987px]]

Configuring Modbus TCP Master, MQTT Gateway MQTT Broker on RUT240, and MQTT Publisher/Subscriber on PC


The same configuration will be used for Modbus TCP Master and Slave {{{name}}} routers as in the previous example, only settings in Modbus TCP Master router {{{name}}} will be changed to match MQTT Broker on RUT240 router

Navigate to Services → Modbus MQTT Gateway

  1. Enable
  2. Host: Enter Public IP address of MQTT Broker (RUT240)
  3. Username: N/A
  4. Password: N/A
  5. Press Save & Apply

Configuring RUT240 MQTT Broker


Navigate to Services → MQTT → Broker

  1. Select Enable
  2. Check Enable Remote Access
  3. Press Save & Apply

Testing MQTT Gateway


For testing purposes, two terminal windows will be used on the same PC.

To get Ubuntu terminal on Windows 10/11, refer to the following link for instructions: https://tutorials.ubuntu.com/tutorial/tutorial-ubuntu-on-windows#0

  • Open first terminal, which will act as Subscriber. Type in:

mosquito_sub -h [Host_address] -p [Port] -t [Topic]

  • Open second terminal, which will act as Publisher. Type in:

mosquito_pub -h [Host] -h [Host_address] -p [Port] -m [‘Message’] -t [Topic]

  • On the first window - Subscriber, a response should appear

See Also