Template:Networking rutos manual input output pinout: Difference between revisions
No edit summary |
No edit summary |
||
Line 46: | Line 46: | ||
<li><b>Output</b>: digital open collector (OC) output; 30 V, 300 mA.</li>}} | <li><b>Output</b>: digital open collector (OC) output; 30 V, 300 mA.</li>}} | ||
</ul>}} | </ul>}} | ||
{{#switch: {{{name}}} | |||
| TRB141 =<h3>Input/Output Connector Pinout</h3> | |||
---- | |||
[[File:Networking_trb141_manual_input_output_input_output_connector_pinout_v2.png]] | |||
<ul> | |||
<li><b>DI<sub>1</sub></b> & <b>DI<sub>2</sub></b> - DRY/WET configurable inputs: | |||
<ul> | |||
<li><b>WET</b>: 0-1.9 V is detected as logical "0"; 1.9-3.8 V is detected as logical "1"</li> | |||
<li><b>DRY</b>: is detected as logical "0" when the input is shorted to GND; otherwise is detected as logical "1"</li> | |||
</ul> | |||
</li> | |||
<li><b>NC<sub>1</sub></b>, <b>C<sub>1</sub></b> & <b>NO<sub>1</sub></b> - Normally Closed, Common and Normally Open contacts of the internal Non-Latching Relay respectively.<br>Maximum relay ratings: 0.5 A at 60 VDC/70 VAC, 1 A at 30 VDC/VAC.</li> | |||
<li><b>NC<sub>2</sub></b>, <b>C<sub>2</sub></b> & <b>NO<sub>2</sub></b> - Normally Closed, Common and Normally Open contacts of the internal Latching Relay respectively.<br>Maximum relay ratings: 0.8 A at 70 VDC, 0.9 A at 70 VAC, 2 A at 30 VDC/VAC.</li> | |||
<li><b>A</b> - ADC input. Analog voltage range: 0-30 V. The input can be configured for 4-20 mA sensor protocol as current measurement (ACL) of 0-30 mA.</li> | |||
<li><b>l</b> and <b>⏚</b> - isolated input contacts. | |||
<ul> | |||
<li>0-7.3 V is detected as logical "0"</li> | |||
<li>7.3-71 V is detected as logical "1"</li> | |||
</ul> | |||
</li> | |||
<li><b>+</b> - a power output connected directly to gateway's power supply input pin. This Output can be used to power an external 4-20 mA current sensor.</li> | |||
<li><b>3.8</b> is a 3.8 V power output that can be used to power 1-Wire sensors.</li> | |||
<li><b>1W</b> - 1-Wire protocol input/output.</li> | |||
<li><b>⏚</b> - GND contact.</li> | |||
<li><b>''Note:''</b> input circuit components have tolerance of +-1%.</li> | |||
</ul> | |||
| RUT955|RUT956|RUT906 =<h3>Input/Output Connector Pinout</h3> | |||
---- | |||
[[File:Networking_rut955_manual_input_output_input_output_connector_pinout_v3.png]] | |||
<ul> | |||
<li><b>DI</b><sub>1</sub> and <b>⏚</b><sub>1</sub> - Digital input (dry type):</li> | |||
<ul> | |||
<li>0-1.2 V is detected as logical "1"</li> | |||
<li>1.8-3 V is detected as logical "0"</li> | |||
</ul> | |||
<li><b>DI</b><sub>2</sub> and <b>⏚</b><sub>2</sub> - Digital galvanically isolated input:</li> | |||
<ul> | |||
<li>0-4 V is detected as logical "0"</li> | |||
<li>9-30 V is detected as logical "1"</li> | |||
</ul> | |||
<li><b>DO</b> and <b>⏚</b><sub>3</sub> - Galvanically isolated open collector (OC) output: 30 V, 250 mA.</li> | |||
<li><b>+V</b> and <b>⏚</b><sub>3</sub> - External VCC for <b>DO</b> (<30 V).</li> | |||
<li><b>C & NO</b> - Common and Normally Open contacts of the internal Non-Latching Relay respectively.<br>Maximum relay ratings: 4 A at 24 VDC, 4 A at 40 VAC.</li> | |||
<li><b>A</b> and <b>⏚</b><sub>1</sub> - ADC input. Analog voltage range: 0-24 V. The input can be configured for 4-20 mA sensor protocol as current measurement (ACL).<span class="asterisk">*</span></li> | |||
<li><b>⏚</b><sub>1</sub> - GND for <b>DI</b><sub>1</sub> and <b>A</b>.</li> | |||
<li><b>⏚</b><sub>2</sub> - GND for <b>DI</b><sub>2</sub>. | |||
<li><b>⏚</b><sub>3</sub> - GND for <b>DO</b> pins. | |||
<li><b>''Note:''</b> input circuit components have tolerance of +-1%.</li> | |||
</ul> | |||
---- | |||
<span class="asterisk">*</span> The deviation from the actual input voltage and the voltage measured by the device is dependent on the input voltage value: | |||
<ul> | |||
<li>'''≥ 1.5 V''' - the deviation is about ± 10 % and gets lower when the input voltage increases towards 5 V</li> | |||
<li>'''≥ 5 V''' - the deviation does not exceed ± 3 %</li> | |||
<li>'''≥ 9 V''' - the deviation does not exceed ± 2 %</li> | |||
</ul> | |||
<b>Additional note</b>: the deviation values specified above are applicable in temperatures of < 50 °C. Under higher temperatures the deviation values become considerably higher. | |||
}} |
Revision as of 09:24, 2 December 2024
Power Socket Pinout
[[File:Networking_rutos_manual_input_output_power_socket_pinout_configurableio_{{{configurableio}}}.png]]
- Power: {{{input_volts}}} VDC positive (+).
- Ground: negative/ground (-).
- Input: digital non-isolated input.
- logical low level: 0 - 5 V;
- logical high level: 8 - 30 V.
- Output: digital open collector (OC) output; 30 V, 300 mA.