Template:Networking manual Modbus serial RutOS: Difference between revisions
Line 149: | Line 149: | ||
[[File:BeeceptorData.png|border|class=tlt-border|]] | [[File:BeeceptorData.png|border|class=tlt-border|]] | ||
Try to change some data in the Modbus | Try to change some data in the Modbus Serial server simulator (ModRSsim). | ||
[[File:Modbus serial rut955 10.png|border|class=tlt-border|700x700px]] | [[File:Modbus serial rut955 10.png|border|class=tlt-border|700x700px]] |
Latest revision as of 11:57, 29 August 2024
Summary
Modbus is a serial communications protocol originally published by Modicon (now Schneider Electric) in 1979 for use with its programmable logic controllers (PLCs). Modbus has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices. The main reasons for the use of Modbus in the industrial environment are:
- developed with industrial applications in mind;
- openly published and royalty-free;
- easy to deploy and maintain;
- moves raw bits or words without placing many restrictions on vendors.
Modbus enables communication among many devices connected to the same network, for example, a system that measures temperature and humidity and communicates the results to a computer. Modbus is often used to connect a supervisory computer with a remote terminal unit (RTU) in supervisory control and data acquisition (SCADA) systems. Many of the data types are named from its use in driving relays: a single-bit physical output is called a coil, and a single-bit physical input is called a discrete input or a contact.
This article provides a brief example on how to use Modbus serial to monitor a slave device, send data to server and how to configure slave alarms. To find more information about this feature visit RUT955 Modbus page.
Prerequisites
- One device with RS232 Serial port;
- Windows 10/11 OS computer;
- Beeceptor account and created Mock server;
- ModRSsim application;
- RS232 to USB cable.
Topology
Installation
From FW version of RUT9_R_00.07.05 and newer Modbus Serial Client package is installed by default. To install it on older FW versions open device's WebUI, navigate to Services → Package manager → Packages and search for Modbus Serial Master and press + icon to install. After installation you should see a status Installed on this package.
Configuring Modbus Serial server device
In this example we are going to be using our Windows 10/11 OS computer as a slave. To do so you will need to install modRSsim application, which you can download here.
When you are done with that, open the app and apply the following configuration.
|
|
Configuring Modbus serial master
Open router’s WebUI, navigate to Services → Modbus → Modbus Serial Client and in Serial Device configuratio section add new instance by entering a name, selecting rs232 and pressing button. In the newly opened Device Configuration window configure everything as follows:
Now in Modbus Devices section create RS232 slave by writing a new instance name, selecting rs232 and pressing button. In the new window apply the following configuration:
Modbus data to server
Creating server
In order to test the functionality, you will need to set up a server.
There are many ways how you can create a server to which Modbus will send data to. In this example we are going to be using a Beeceptor's Mock server. If you don't have a Beeceptor account yet – create it or login via Google account.
|
And that is it, now you will be able to see the data coming from Modbus to your created Beeceptor's server.
RUT Modbus data to server configuration
In order to setup your router to send Modbus data to server you will need to navigate to Services → Data to Server, create a "New collectiom name" and press ADD to add a new instance.
- Select Type: Modbus;
- Select Format Type: Custom;
- Enter desired format string;
- Leave other parameterms as it is and click on icon;
- In the Collection configuration window leave the settings as default and click on button;
- In the Server configuration window select Type: HTTP;
- Enter Server address;
- Click ;
Receiving data
Open Beeceptor's window again, and after some time you should start receiving Modbus Data messages.
Try to change some data in the Modbus Serial server simulator (ModRSsim).
Received data should change.
Server alarms
In order to setup the following configuration SIM card is required.
Go back to Services → Modbus → Modbus Serial Client and press button on the previously created Modbus server Device instance or create a new one. In the opened window scroll down to the bottom and in Alarms Configuration section press .
In Alarm Configuration apply the following changes:
Now go back to Modbus server simulator and edit this window:
Change the value to anything below 10, you should not receive messages. Then change the value to anything above 10, you should start receiving messages.