Template:Networking rut manual modbus: Difference between revisions
No edit summary |
|||
Line 1: | Line 1: | ||
==Summary== | ==Summary== | ||
<b>Modbus</b> is a serial communications protocol. Simple and robust, it has | <b>Modbus</b> is a serial communications protocol. Simple and robust, it has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices. This chapter is an overview of the Modbus TCP functionality for {{{name}}} devices. | ||
{{Template: Networking_rutxxx_manual_fw_disclosure | {{Template: Networking_rutxxx_manual_fw_disclosure |
Revision as of 13:15, 23 July 2019
Summary
Modbus is a serial communications protocol. Simple and robust, it has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices. This chapter is an overview of the Modbus TCP functionality for {{{name}}} devices.
The information in this page is updated in accordance with the [[Media:{{{fw_version}}}_WEBUI.bin|{{{fw_version}}}]] firmware version.
Modbus TCP
Modbus TCP provides users with the possibility to set or get system parameters. The Modbus daemon acts as slave device. That means it accepts connections from a master (client) and sends out a response or sets some system related parameter in accordance with the given query.
The figure below is an example of the Modbus TCP window section and the table below provides information on the fields contained in that window:
[[File:{{{file_modbus_tcp}}}]]
Template:Networking rut9xx manual modbus modbus tcp table
Get Parameters
Modbus parameters are held within registers. Each register contains 2 bytes of information. For simplification, the number of registers for storing numbers is 2 (4 bytes), while the number of registers for storing text information is 16 (32 bytes). The register numbers and corresponding system values are described in the table below:
{{Template: Networking_{{{name}}}_manual_modbus_modbus_tcp_get_parameters_table}}
Set Parameters
The Modbus daemon can also set some device parameters. These parameters and explanations on how to use them are described in the table below:
{{Template: Networking_{{{name}}}_manual_modbus_modbus_tcp_set_parameters_table}}
* All ON/OFF commands only accept 0 and 1 values, which represent the following:
- 1 - ON
- 0 - OFF
Modbus TCP Master
A Modbus master device can request data from Modbus slaves. The Modbus TCP Master section is used to configure Modbus TCP slaves. To add a new slave, enter a custom name, slave's ID, IP address and port and click the "Add" button: [[File:{{{file_add_new_slave}}}]]
Button | Description |
---|---|
Edit | Redirects you to the slave's configuration page (more information in [[{{{name}}} Modbus#Slave_device_configuration|section 3.1]]) |
Delete | Deletes the slave configuration |
Alarms | Redirects you to the slave's alarm configuration page (more information in [[{{{name}}} Modbus#Alarm_configuration|section 3.3]]) |
Clone | Creates an identical slave configuration |
You can create a maximum of 10 slave configurations.
Slave device configuration
The figure below is an example of the Slave device configuration and the table below provides information on the fields contained in that section:
[[File:{{{file_slave_configuration}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns communication with the slave device on or off. |
Name | string; default: none | Slave device's name, used for easier management purposes. |
Slave ID | integer [0..255]; default: none | Slave ID. Each slave in a network is assigned a unique identifier ranging from 1 to 255. When the master requests data from a slave, the first byte it sends is the Slave ID. When set to 0, the slave will respond to requests addressed to any ID. |
IP address | ip; default: none | Slave device's IP address. |
Port | integer [0..65535]; default: none | Slave device's Modbus TCP port. |
Period | integer [1..6400]; default: none | Interval at which requests are sent to the slave device. |
Timeout | integer [1..30]; default: none | Maximum response wait time. |
Requests configuration
A Modbus request is way of obtaining data from Modbus slaves. The master sends a request to a slave specifying which Modbus registers should be read. The slave then sends the requested data back to the Modbus master. You can create a maximum of 64 request configurations for each slave device.
The figure below is an example of the Requests configuration section and the table below provides information contained in the fields of that section:
[[File:{{{file_requests}}}]]
Field | Value | Description |
---|---|---|
Name | string; default: Unnamed Parameter | Request name. Used for easier management purposes. |
Data type | 8bit INT | 8bit UINT | 16bit INT, high byte first | 16bit INT, low byte first | 16bit UINT, high byte first | 16bit UINT, low byte first | 32bit float, Byte order 1,2,3,4 | 32bit float, Byte order 4,3,2,1 | 32bit float, Byte order 2,1,4,3 | 32bit float, Byte order 3,4,1,2; default: 16bit INT, high byte first | How read data will be stored. |
Function | 1 | 2 | 3 | 4 | 5 | 6 | 15 | 16; default: 3 | A function code specifies the type of register being addressed by a Modbus request. The codes represent these functions:
|
First Register | integer [0..65535]; default: 1 | First Modbus register from which data will be read. |
Number of Registers | integer [1..2000]; default: none | Number of Modbus registers that will be read during the request. |
Enabled | yes | no; default: no | Turns the request on or off. |
Test | - (interactive button) | Generates a Modbus request according to given parameters in order to test the request configuration. You must first save the configuration before you can use the Test button. |
Delete | - (interactive button) | Deletes the request. |
Add | - (interactive button) | Adds a new request configuration. |
Alarm configuration
Alarms are way of setting up automated actions when some Modbus values meet user specified conditions. The figure below is an example of the Alarm configuration page and the table below provides information on fields that it contains:
[[File:{{{file_alarms}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the alarm on or off |
Function code | Read Coil Status (1) | Read Input Status (2) | Read Holding Registers (3) | Read Input Registers (4); default: Read Coil Status (1) | Modbus function used in Modbus request. |
Register | integer [0..65535]; default: none | Number of the Modbus coil/input/holding register/input register that will be read. |
Condition | More than | Less than | Equal to | Not Equal to; default: Equal to | When a value is obtained it will be compared against the value specified in the following field. The comparison will be made in accordance with the condition specified in this field. |
Value | various; default: none | The value against which the read data will be compared. |
Action | SMS | Trigger output | Modbus Request; default: SMS | Action that will be taken if the condition is met. Possible actions:
|
SMS: Message | string; default: none | SMS message text. |
SMS: Phone number | phone number; default: none | Recipient's phone number. |
Trigger output: Output | Open collector output | Relay output | Both; default: Open collector output | Which output(s) will be triggered. |
Trigger output: I/O Action | Turn On | Turn Off | Invert; default: Turn On | Action that will taken on the specified output. |
Modbus Request: IP address | ip | host; default: none | Modbus slave's IP address. |
Modbus Request: Port | integer [0..65535]; default: none | Modbus slave's port. |
Modbus Request: Timeout | integer [1..30]; default: 5 | Maximum time to wait for a response. |
Modbus Request: ID | integer [1..255]; default: none | Modbus slave ID. |
Modbus Request: Modbus function | Read Coil Status (1) | Read Input Status (2) | Read Holding Registers (3) | Read Input Registers (4) | Force Single Coil (5) | Preset Single Register (6) | Force Multiple Coils (15) | Force Multiple Registers (16); default: Force Single Coil (5) | A function code specifies the type of register being addressed by a Modbus request. |
Modbus Request: First register | integer [0..65535]; default: none | Begins reading from the register specified in this field. |
Modbus Request: Number of registers | integer [0..65535]; default: none | The number of registers that will be read from the first register. |
Modbus Serial Master
RS232
[[File:{{{file_rs232}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the Modbus RTU via RS232 on or off. |
Baud rate | 300 | 1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200; default: 19200 | Serial data transmission rate (in bits per second). |
Data bits | 5 | 6 | 7 | 8; default: 8 | Number of data bits of each character. |
Parity | None | Even | Odd; default: Even | In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
|
Stop bits | 1 | 2; default: 1 | Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used. |
Flow control | None | RTS/CTS | Xon/Xoff; default: None | In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
|
RS485
[[File:{{{file_rs485}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the Modbus RTU via RS485 on or off. |
Baud rate | 300 | 1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200; default: 19200 | Serial data transmission rate (in bits per second). |
Data bits | 5 | 6 | 7 | 8; default: 8 | Number of data bits of each character. |
Parity | None | Even | Odd; default: Even | In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
|
Stop bits | 1 | 2; default: 1 | Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used. |
Flow control | None | RTS/CTS | Xon/Xoff; default: None | In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
|
Slaves
[[File:{{{file_slave_settings}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the slave on or off. |
Slave ID | integer [1..255]; default: 1 | Slave ID. Each slave in a network is assigned a unique identifier randging from 1 to 255. When the master requests data from a slave, the first byte it sends is the Slave ID. |
Period | integer [1..9999]; default: 10 | Interval (in minutes) at which requests are sent to the slave device. |
Slave requests
[[File:{{{file_slave_request}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the request on or off. |
Function | Read Coil | Read Discrete Input | Read Holding Registers | Read Input Registers; default: Read Holding Registers | Modbus function used in Modbus request. |
First Register | integer [1..65536]; default: 1 | First Modbus register from which data will be read. |
Number of Registers | integer [1..2000]; default: none | Number of Modbus registers that will be read during the request/ |
Slave alarms
[[File:{{{file_slave_alarm}}}]]
Field | Value | Description |
---|---|---|
Enabled | yes | no; default: no | Turns the alarm on or off. |
Function | Read Coil | Read Discrete Input | Read Holding Registers | Read Input Registers; default: Read Holding Registers | Modbus function used in Modbus request. |
Register | integer [1..65536]; default: 1 | Number of the Modbus coil/input/holding register/input register that will be read. |
Condition | More than | Less than | Equal to | Not equal to; default: More than | When a value is obtained it will be compared against the value specified in the following field. The comparison will be made in accordance with the condition specified in this field. |
Value | integer [0..65535]; default: 0 | The value against which the read data will be compared. |
Action | SMS | Trigger output | Modbus request; default: SMS | Action that will be taken if the condition is met. Possible actions:
|
Modbus Data to Server
The Modbus Data to Server function provides you with the possibility to set up senders that transfer data collected from Modbus slaves to remote servers. To add a new data sender, enter the server's address, specify the data sending period and click the "Add" button:
[[File:{{{file_add_new_sender}}}]]
Data sender configuration
When you add a new data sender, you will be redirected to its configuration window. The figure below is an example of that window and the table below provides information on the fields that it contains:
[[File:{{{file_sender_configuration}}}]]
Enabled | yes | no; Default: no | Turns the data sender ON or OFF |
---|---|---|
Name | string; Default: none | Data sender's name. used for easier management purposes |
Protocol | HTTP(S); Default: HTTP(S) | Data sending protocol |
JSON format | json string; Default: {"ID":"%i", "TS":"%t","ST":"%s","VR":"%a"} | Provides the possibility to fully customize the JSON segment |
Segment count | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10; Default: 1 | Max segment count in one JSON string sent to server |
URL | host | ip; Default: none | Address of the server to which the data will be sent. . Important note: when using HTTPS, remember to add the https:// prefix before the URL |
Period | integer [1..6400]; Default: none | Data sending frequency (in seconds) |
Data filtering | All data | By slave ID | By slave IP; Default: All data | Which data this sender will transfer to the server |
Retry on fail | yes | no; Default: no | Specifies whether the data sender should retry failed attempts |
Custom header | string; Default: no | Adds a custom header(s) to HTTP requests |
See also
Template:Networking device modbus see also
[[Category:{{{name}}} WebUI]]