Difference between revisions of "Template:Networking rutos manual bacnet"

From Teltonika Networks Wiki
Line 20: Line 20:
 
==General Configuration==
 
==General Configuration==
  
[[File:Networking_rutos_manual_bacnet_general_configuration_v2.png|border|class=tlt-border]]
+
[[File:Networking_rutos_manual_bacnet_general_configuration_v3.png|border|class=tlt-border]]
  
 
<table class="nd-mantable">
 
<table class="nd-mantable">
Line 35: Line 35:
 
     <tr>
 
     <tr>
 
         <td>Enable BBMD</td>
 
         <td>Enable BBMD</td>
         <td>off | on; default: <b>off</b></td>
+
         <td>off | <span style="color:blue">on</span>; default: <b>off</b></td>
 
         <td>Enables BACnet broadcast management function.</td>
 
         <td>Enables BACnet broadcast management function.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>BBMD interface</td>
+
         <td><span style="color:blue">BBMD port</span></td>
 +
        <td>integer [1..65535]; default: <b>47809</b></td>
 +
        <td>BACnet broadcast management devices port.</td>
 +
    </tr>
 +
    <tr>
 +
        <td><span style="color:blue">BBMD interface</span></td>
 
         <td>network interface; default: <b>eth0</b></td>
 
         <td>network interface; default: <b>eth0</b></td>
 
         <td>Specifies interface for BBMD function. IP address of this interface should be reachable from WAN.</td>
 
         <td>Specifies interface for BBMD function. IP address of this interface should be reachable from WAN.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>Allow Remote Access</td>
+
         <td><span style="color:blue">Allow Remote Access</span></td>
 
         <td>off | on; default: <b>off</b></td>
 
         <td>off | on; default: <b>off</b></td>
 
         <td>Creates port forward firewall rule to make application port in LAN reachable from selected BBMD interface.</td>
 
         <td>Creates port forward firewall rule to make application port in LAN reachable from selected BBMD interface.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>Force gateway</td>
+
         <td><span style="color:blue">Force gateway</span></td>
         <td>off | on; default: <b>off</b></td>
+
         <td>off | <span style="color:red">on</span>; default: <b>off</b></td>
 
         <td>Adds configured gateway IP address and port to BBMD packages sent.</td>
 
         <td>Adds configured gateway IP address and port to BBMD packages sent.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>Gateway address</td>
+
         <td><span style="color:red">Gateway address</span></td>
 
         <td>ip4; default: <b>none</b></td>
 
         <td>ip4; default: <b>none</b></td>
 
         <td>Gateway IP address.</td>
 
         <td>Gateway IP address.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>Gateway port</td>
+
         <td><span style="color:red">Gateway port</span></td>
 
         <td>integer [1..65535]; default: <b>none</b></td>
 
         <td>integer [1..65535]; default: <b>none</b></td>
 
         <td>Gateway port number.</td>
 
         <td>Gateway port number.</td>
Line 69: Line 74:
 
Communications in BACnet over IP (<b>BIP</b>) rely upon the protocol rules of IP and Ethernet.
 
Communications in BACnet over IP (<b>BIP</b>) rely upon the protocol rules of IP and Ethernet.
  
[[File:Networking_rutos_manual_bacnet_bip_configuration_v1.png|border|class=tlt-border]]
+
[[File:Networking_rutos_manual_bacnet_bip_configuration_v2.png|border|class=tlt-border]]
  
 
<table class="nd-mantable">
 
<table class="nd-mantable">
Line 78: Line 83:
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>
         <td>BIP port</td>
+
         <td>Network ID</td>
 +
        <td>integer [1..65535]; default: <b>1</b></td>
 +
        <td>Unique identifier for the BACnet/IP subnet within the entire BACnet internetwork.</td>
 +
    </tr>
 +
    <tr>
 +
        <td>Port</td>
 
         <td>integer [1..65535]; default: <b>47808</b></td>
 
         <td>integer [1..65535]; default: <b>47808</b></td>
         <td>BIP UDP port.</td>
+
         <td>This specifies the port number used by BACnet/IP devices for communication..</td>
 +
    </tr>
 +
    <tr>
 +
        <td>Device</td>
 +
        <td>interface; default: <b>br-lan</b></td>
 +
        <td>Select the network device to be used for BACnet/IP communication.</td>
 +
    </tr>
 +
    <tr>
 +
        <td>Actions</td>
 +
        <td>-interactive button; default: <b>delete</b></td>
 +
        <td>Deletes BIP configuration.</td>
 
     </tr>
 
     </tr>
 
</table>
 
</table>
Line 88: Line 108:
 
<b>MSTP</b> is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 31 devices to be installed on a single network.
 
<b>MSTP</b> is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 31 devices to be installed on a single network.
  
[[File:Networking_rutos_manual_bacnet_mstp_configuration_v2.png|border|class=tlt-border]]
+
[[File:Networking_rutos_manual_bacnet_mstp_configuration_v3.png|border|class=tlt-border]]
  
 
<table class="nd-mantable">
 
<table class="nd-mantable">
Line 95: Line 115:
 
         <th>Value</th>
 
         <th>Value</th>
 
         <th>Description</th>
 
         <th>Description</th>
 +
    </tr>
 +
    <tr>
 +
        <td>Network ID</td>
 +
        <td>integer [1..65535]; default: <b>2</b></td>
 +
        <td>Unique identifier for the BACnet MSTP network.</td>
 
     </tr>
 
     </tr>
 
     <tr>
 
     <tr>

Revision as of 14:30, 3 October 2024

The information in this page is updated in accordance with firmware version .

Summary

BACnet is a communication protocol for building automation and control (BAC) networks that use the ASHRAE, ANSI, and ISO 16484-5 standards protocol.

This manual page provides an overview of the BACnet functionality in {{{name}}} devices.

Note: BACnet is additional software that can be installed from the System → [[{{{name}}} Package Manager|Package Manager]] page.

General Configuration

Networking rutos manual bacnet general configuration v3.png

Field Value Description
Enable off | on; default: off Enables BACnet router function.
Enable BBMD off | on; default: off Enables BACnet broadcast management function.
BBMD port integer [1..65535]; default: 47809 BACnet broadcast management devices port.
BBMD interface network interface; default: eth0 Specifies interface for BBMD function. IP address of this interface should be reachable from WAN.
Allow Remote Access off | on; default: off Creates port forward firewall rule to make application port in LAN reachable from selected BBMD interface.
Force gateway off | on; default: off Adds configured gateway IP address and port to BBMD packages sent.
Gateway address ip4; default: none Gateway IP address.
Gateway port integer [1..65535]; default: none Gateway port number.

BIP Configuration

Communications in BACnet over IP (BIP) rely upon the protocol rules of IP and Ethernet.

Networking rutos manual bacnet bip configuration v2.png

Field Value Description
Network ID integer [1..65535]; default: 1 Unique identifier for the BACnet/IP subnet within the entire BACnet internetwork.
Port integer [1..65535]; default: 47808 This specifies the port number used by BACnet/IP devices for communication..
Device interface; default: br-lan Select the network device to be used for BACnet/IP communication.
Actions -interactive button; default: delete Deletes BIP configuration.

MSTP Configuration

MSTP is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 31 devices to be installed on a single network.

Networking rutos manual bacnet mstp configuration v3.png

Field Value Description
Network ID integer [1..65535]; default: 2 Unique identifier for the BACnet MSTP network.
MSTP MAC integer [0..127]; default: 13 Router MSTP MAC address.
MSTP MAC max integer [1..127]; default: 127 Maximum client address in the MSTP network.
Baud rate 300 | 600 | 1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200 | 230400; default: 38400 Serial data transmission rate (in bits per second).
Parity Even | Odd | Mark | Space | None; default: None In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
  • None (N) - no parity method is used.
  • Odd (O) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.
  • Even (E) - the parity bit is set so that the number of "logical ones (1s)" has to be even.
  • Space (S) - the parity bit will always be a binary 0.
  • Mark (M) - the parity bit will always be a binary 1.
Data bits 5 | 6 | 7 | 8; default: 8 Number of data bits for each character.
Stop bits 1 | 2; default: 1 Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used..

[[Category:{{{name}}} Services section]]