Main Page > RUT Routers > RUT956 > RUT956 Manual > RUT956 WebUI > RUT956 Services section > RUT956 Serial Utilities

The information in this page is updated in accordance with firmware version RUT9_R_00.07.11.3.

Note: click here for the old style WebUI (FW version RUT9XX_R_00.06.09.5 and earlier) user manual page.

Summary

The Serial Utilities page is used to make serial communication configurations of different types. This manual page provides an overview of the Serial Utilities page in RUT956 devices.

General information

RS232


Connector pinout


The following table lists commonly used RS-232 signals (DTE male to DCE female). The RS232 connector type on device is a DCE female.

PIN NAME* DESCRIPTION* DIRECTION ON THIS DEVICE
1 DCD Data Carrier Detect Input
2 RXD Receive Data Input
3 TXD Transmit Data Output
4 DTR Data Terminal Ready Output
5 GND Signal Ground -
6 DSR Data Set Ready Input
7 RTS Ready To Send Output
8 CTS Clear To Send Input
9 RI Ring Indicator Input (connected to +5V permanently via a 4.7k resistor)

Cables


There are two types of RS232 serial devices: DTE and DCE. DTE typically refers to the serial port on a PC or terminal, while DCE refers to communication devices. Connectors mounted on DTE are likely to be male, and those mounted on DCE are likely to be female.

This device is DCE and has a female connector.


To connect a standard DTE device, use a straight-through Female/Male RS232 cable:

See straight cable pinout below:


To connect another DCE device to RUT/TRB, a Null-modem (crossed) Male/Male cable should be used:

See straight crossed cable pinout below:


Maximum cable length is 15 meters or the cable length equal to a capacitance of 2500 pF (for a 19200 baud rate). Using lower capacitance cables can increase the distance. Reducing communication speed can also increase maximum cable length.

RS485


Connector pinout


Below is a depiction of the RS485 connector pins:

RS485 connector pinout
Pin Name Description
1 D_N Driver negative signal
2 R_N Receiver negative signal
3 GND Device ground
4 D_P Driver positive signal
5 R_P Receiver positive signal
6 NC Power input 9-30 VDC filler text

Cable type


Recommended cable parameters:

PARAMETER VALUE
Cable Type 22-24 AWG, 2 – pair (used for full-duplex networks ) or 1-pair (used for half duplex networks). One addtitional wire for ground connection is needed
Characteristic cable Impedance 120 Ω @ 1MHz
Capacitance (conductor to conductor) 36 pF/m
Propagation Velocity 78% (1.3 ns/ft)

Maximum data rate vs. transmission line length


The RS485 standard can be used for network lengths up to 1200 meters, but the maximum usable data rate decreases as the transmission length increases. A device operating at the maximum data transfer rate (10 Mbps) is limited to a transmission length of about 12 meters, while a distance up to 1200 meters can be achieved at 100 Kbps. A rough relation between maximum transmission length and data rate can be calculated using this approximation:

Where:

  • Lmax - maximum cable length in meters.
  • DR - maximum data rate in bits per second.

Twisted pair is the preferred cable type for RS485 networks. Twisted pair cables pick up noise and other electromagnetically induced voltages as common mode signals, which are rejected by the differential receivers.

2-Wire and 4-Wire Networks


Below is an example of a 4-wire network electrical connection. There are 3 devices shown in the example. One of the devices is the "master" and other two are "slaves". Termination resistors (120 Ω each) are placed at each cable end. Four-wire networks consists of one master with its transmitter connected to each of the slaves' receivers on one twisted pair. The slave transmitters are all connected to the master receiver on a second twisted pair:

Example 2-wire network electrical connection: to enable a 2-wire RS485 configuration you need to connect D_P to R_P and D_N to R_N on the device’s RS485 socket. Termination resistors are placed at each cable end (120 Ω each):

Modem Control

The Modem serial type is used to manage modem functionality which could be accessed using shell interface. For this purpose you may want use CR/LF (Carriage Return, Line Feed) capable applications like PuTTY on Windows and microcom, minicom, cutecom or similar applications on Linux.

Status

General settings

Field Value Description
Enable off | on; default: off Turns the instance on or off.
Name string; default: none Instance name, generated by the user when first creating the configuration.
Device RS232 | RS485 | USB RS232 interface; default: RS232 Specifies which serial port will be used for serial communication.
Baud rate (RS485) integer [300..230400]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (RS232) integer [300..115200]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (USB) integer [300..4000000]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Data bits 5 | 6 | 7 | 8; default: 8 Number of data bits for each character.
Stop bits 1 | 2; default: 1 Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used.
Parity None | Odd | Even | Mark | Space; default: None In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
  • None (N) - no parity method is used.
  • Odd (O) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.
  • Even (E) - the parity bit is set so that the number of "logical ones (1s)" has to be even.
Flow control None| RTS/CTS | Xon/Xoff; default: None In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
  • RTS/CTS - hardware handshaking. RTS and CTS are turned OFF and ON from alternate ends to control data flow, for instance when a buffer is almost full.
  • Xon/Xoff - software handshaking. The Xon and Xoff characters are sent by the receiver to the sender to control when the sender will send data, i.e., these characters go in the opposite direction to the data being sent. The circuit starts in the "sending allowed" state. When the receiver's buffers approach capacity, the receiver sends the Xoff character to tell the sender to stop sending data. Later, after the receiver has emptied its buffers, it sends an Xon character to tell the sender to resume transmission.
Mode Partial control | Full control; default: Partial control Specifies modem control mode.
  • Partial control- enables modem control with AT commands, mobile connection will be controlled by RUTOS.
  • Full control- enables modem control with AT commands, mobile connection will be controlled by user.
RS485: Full Duplex off | on; default: off Turns Full Duplex mode on or off. This option is available only on the RS485 device.

Advanced settings

Field Value Description
Start up message string; default: none Prints message to serial device when modem control is ready.
Canonical mode off | on; default: off Forwards data to modem only when new line symbol ('\n') is detected.

Console

Console mode requires no further configuration than the settings above and is used as a direct-access method to the device's shell interface. For this purpose you may want use such applications as PuTTY on Windows and microcom, minicom, picocom or similar applications on Linux.

Status

General settings

Field Value Description
Enable off | on; default: off Turns the instance on or off.
Name string; default: none Instance name, generated by the user when first creating the configuration.
Device RS232 | RS485 | USB RS232 interface; default: RS232 Specifies which serial port will be used for serial communication.
Baud rate (RS485) integer [300..230400]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (RS232) integer [300..115200]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (USB) integer [300..4000000]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Data bits 5 | 6 | 7 | 8; default: 8 Number of data bits for each character.
Stop bits 1 | 2; default: 1 Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronize with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used.
Parity None | Odd | Even | Mark | Space; default: None In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
  • None (N) - no parity method is used.
  • Odd (O) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.
  • Even (E) - the parity bit is set so that the number of "logical ones (1s)" has to be even.
Flow control None| RTS/CTS | Xon/Xoff; default: None In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
  • RTS/CTS - hardware handshaking. RTS and CTS are turned OFF and ON from alternate ends to control data flow, for instance when a buffer is almost full.
  • Xon/Xoff - software handshaking. The Xon and Xoff characters are sent by the receiver to the sender to control when the sender will send data, i.e., these characters go in the opposite direction to the data being sent. The circuit starts in the "sending allowed" state. When the receiver's buffers approach capacity, the receiver sends the Xoff character to tell the sender to stop sending data. Later, after the receiver has emptied its buffers, it sends an Xon character to tell the sender to resume transmission.
RS485: Full Duplex off | on; default: off Turns Full Duplex mode on or off. This option is available only on the RS485 device.

Over IP

The Over IP serial type is used to manage serial connections over a TCP/IP network.

Instance Example


Here's an example demonstrating Over IP in action, running in Client + Server Mode.

Serial Device Configuration


Configure serial port communication parameters in the Serial Device Configuration section.

[[File:Networking_rutos_manual_serial_utilities_over_ip_serial_default_{{{default}}}_v2.png|border|class=tlt-border]]

Field Value Description
Enable off | on; default: off Turns the instance on or off.
Name string; default: none Instance name, generated by the user when first creating the configuration.
Device RS232 | RS485 | USB RS232 interface; default: RS232 Specifies which serial port will be used for serial communication.
Baud rate (RS485) integer [300..230400]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (RS232) integer [300..115200]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Baud rate (USB) integer [300..4000000]; default:9600 Data rate for serial data transmission (in bits per second (bps)).
Data bits 5 | 6 | 7 | 8; default: 8 Number of data bits for each character.
Stop bits 1 | 2; default: 1 Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used.
Parity None | Odd | Even | Mark | Space; default: None In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
  • None (N) - no parity method is used.
  • Odd (O) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.
  • Even (E) - the parity bit is set so that the number of "logical ones (1s)" has to be even.
Flow control None| RTS/CTS | Xon/Xoff; default: None In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
  • RTS/CTS - hardware handshaking. RTS and CTS are turned OFF and ON from alternate ends to control data flow, for instance when a buffer is almost full.
  • Xon/Xoff - software handshaking. The Xon and Xoff characters are sent by the receiver to the sender to control when the sender will send data, i.e., these characters go in the opposite direction to the data being sent. The circuit starts in the "sending allowed" state. When the receiver's buffers approach capacity, the receiver sends the Xoff character to tell the sender to stop sending data. Later, after the receiver has emptied its buffers, it sends an Xon character to tell the sender to resume transmission.
RS485: Full Duplex off | on; default: off Turns Full Duplex mode on or off. This option is available only on the RS485 device.
RS232: Echo off | on; default: off Enable serial device echo. This option is available only on the RS232 device.

Over IP Configuration Settings


You can configure network related parameters of the serial connection in the Over IP Configuration secion.

Field Value Description
Mode Server | Client | Client + server | Bidirect; default: Server This device's role in the connection:
  • Server - the device waits for incoming connections.
  • Client - the device initiates the connection.
  • Client + server - launches service in server and client(s) mode simultaneously.
  • Bidirect - acts as client by default but waits for incoming connections at the same time.
Protocol TCP | UDP; default: TCP Protocol used in the communication process.
Client: Destination address IP | Port; default: empty Specify server address and port for client to connect to. E.g first field for address second for port. 16 destination addresses are allowed.
Server: UDP: Predefined addresses IP | Port; default: empty Set predefined IP and port for UDP connection. E.g first field for address second for port.
Listening port [1..65535]; default: empty When enabled, all data will be transmitted transparently.

Field Value Description
Use TLS/SSL off | on; default: off Mark to use TLS/SSL for connection.
TLS version Support all | tlsv1.0 | tlsv1.1 | tlsv1.2 | tlsv1.3; default: Support all Minimum TLS version allowed to be used.
TLS type Certificate based | Pre-Shared-Key based; default: Certificate based Select the type of TLS encryption.
Require certificate off | on; default: on Demand certificate and key from peer and verify them against certificate authority.
Verify host off | on; default: off Check if the server certificates Common Name (CN) matches hostname to which client is connecting.
Certificate files from device off | on; default: off Choose this option if you want to select certificate files from device.
Certificate files can be generated <a class=link href="/system/admin/certificates/generation">here</a>.
Certificate file .crt file; default: none Upload certificate file.
Key file .key file; default: none Upload key file.
CA file .ca file; default: none Upload CA file.
Pre-Shared-Key string; default: none The pre-shared-key in hex format with no leading “0x”.
Identify string; default: none Specify the identity.

Field Value Description
Raw mode off | on; default: on When enabled, all data will be transmitted transparently.
Remove all zeros off | on; default: off When checked, indicates that the first hex zeros should be skipped.
Inactivity timeout integer [0..36000]; default: 300 Specifies period of time in seconds, where server connection must be inactive, to disconnect client. To disable timeout input 0.
Serial timeout integer [0..1000]; default: none Specifies the maximum milliseconds to wait for serial data.
Max clients integer [1..32]; default: 4 Specify how many clients are allowed to connect simultaneously.
TCP echo on | off; default: off Enable software TCP echo.
Close connections on | off; default: off Close TCP connections everytime data is sent or received (might result in serial data loss).
Keep alive on | off; default: off Enable keep alive.
Keep alive time integer [0..32000]; default: 0 Close TCP connections everytime data is sent or received (might result in serial data loss).
Keep alive interval integer [0..32000]; default: 0 The interval between subsequential keepalive probes.
Keep alive probes integer [0..32000]; default: 0 The number of unacknowledged probes.

IP Filter


The IP Filter section is used for configuring which network is allowed to communicate with the device. You may add a new instance by selecting the Interface and pressing Add.

Then enter the IP address and save.