Template:Networking rutos manual mbus: Difference between revisions

From Teltonika Networks Wiki
(Created page with "{{Template: Networking_rutos_manual_fw_disclosure | fw_version ={{Template: Networking_rutos_manual_latest_fw | series = {{{series}}} }} }} ==Summary== The <b>M-Bus (Meter...")
 
No edit summary
Line 2: Line 2:
| fw_version ={{Template: Networking_rutos_manual_latest_fw
| fw_version ={{Template: Networking_rutos_manual_latest_fw
  | series = {{{series}}}
  | series = {{{series}}}
| name  = {{{name}}}
  }}
  }}
}}
}}

Revision as of 11:01, 19 May 2022

Template:Networking rutos manual fw disclosure

Summary

The M-Bus (Meter Bus) is a cost-effective fieldbus communication protocol for transmitting energy consumption data. A central master – in this case {{{name}}} – communicates via a two-wire bus (up to max. 250 slaves per segment) with bus devices (e.g., heat meter, water meter, electric meter, gas meter).

This manual page provides an overview of the M-Bus functionality in {{{name}}} devices.

M-Bus Settings

The M-Bus Settings section is used to configure the general service functionality. The figure below is an example of the M-Bus Settings and the table below provides information on the fields contained in that section:

Field Value Description
Enable off | on; default: off Enables the service.
Baud rate 300 | 600 | 1200 | 2400 | 4800 | 9600 | 19200 | 38400; default: 2400 Specifies the M-Bus slave network baud rate.
Database location RAM memory | Flash memory; default: RAM memory Specifies where the database will be stored..

Records

By default there are no Records instances created. To start configuring, add a new record using the Add New Instance section below.

M-Bus Record


The M-Bus Record section is used to configure the general record instance. The figure below is an example of the M-Bus Record and the table below provides information on the fields contained in that section:

Field Value Description
Enable off | on; default: off Enables the service.
Name string; default: none Name used for distinguishing purposes.
Period integer [1..86400]; default: none Specifies the period how often record data will be collected.
String before data string; default: none String that will be appended before request data.
String between data string; default: none String that will be appended between request data.
String after data string; default: none String that will be appended after request data.
Failure mode Never | Any requests failed | All requests failed; default: Never Specifies when whole record is considered as failure.
Store a failure message off | on; default: off Select whether to store a failure message in the database or do nothing on failure.

Request Configuration


In this section, you can configure requests from slaves. By default there are no instances created. To add a new instance and start configuring press the Add button.

Request Configuration Edit


Field Value Description
Enable off | on; default: off Enables request processing.
Slave address int | hexstring; default: none Address of the slave to be inquired.
Data type XML | HEX | BIN; default: XML Data type to process the received data.
Error value string; default: none Changes request data to this value if request fails.
Test configuration button; default: - Tests the current configuration.

Test Configuration


Before saving, you can check if your configuration works accordingly by pressing the Test Configuration button. You should see the data in a field below: