=Summary=
<p style="color:red">The information on this page is updated in accordance with the [https://wiki.teltonika-networks.com/view/FW_%26_SDK_Downloads'''00.07.09'''] firmware version .</p>
Modbus TCP Master section is used for configuring your router as a master device and other routers configured in this section as slave devices. A Modbus TCP master device can then request data from these Modbus TCP slaves.
__TOC__
==Summary==
This article contains instructions on how to configure Modbus TCP functionality on most of the Teltonika Networks devices (with the exception of TAP and TSW series)


First, let’s configure our second router which will be acting as a slave device.  
==Configuration overview & prerequisites==
Before we begin, let's take a look at the configuration that we are attempting to achieve and the prerequisites that make it possible.  


=Configure Modbus TCP slave device=
Configuring port forwarding on Teltonika devices is a simple process that involves just a few steps and can easily be replicated across various devices. The number of devices involved will depend on the specific use case, but the setup can be scaled seamlessly. In the example below, we will use the RUTX50 as the Modbus TCP Client and RUT956 as Modbus TCP Server.
In this example, we would be configuring our slave device to have a 192.168.1.2 internal IP address. This can be done by changing the IP address parameter on Network->WAN page:


[[File:Picture1.png|frame|center|Slave Device Wan Configuration ]]
[[File:Networking Topology Modbus basic config.png|border|class=tlt-border|]]


[[File:Picture2.png|frame|center|Slave Device Wan Configuration Pop menu]]
'''Prerequisites''':
* A device from the RUT, RUTX, RUTM, RUTC or TRB series gateway;
* A PC, Laptop, tablet or a smartphone
* Router acting as Modbus TCP Server must have a SIM card with a Public Static or Public Dynamic IP address (more on IP address types '''[[Private and Public IP Addresses|here]]''') to make remote access possible
* (Optional) If the router's SIM card has a Public Dynamic IP address, you may want to additionally configure a '''[[Dynamic DNS]]''' hostname


Now we need to enable Modbus service for this slave device as we will open a specific port for letting through TCP communications (it is also possible to 'Allow remote access' if we wish to access this router from external WAN using its public IP). This is done on Services->Modbus page:
{{Template:Networking_rutos_manual_basic_advanced_webui_disclaimer
| series = RUTX
}}


[[File:Picture3.png|frame|center|Modbus Slave Configuration]]
=Modbus TCP Server=
Configure Modbus TCP Server device. our slave device to have a 192.168.1.2 internal IP address. This can be done by changing the IP address parameter on Network → WAN page:


=Configuring Modbus TCP master device=
==Modbus TCP Server configuration==
Setup router as Modbus TCP Server. It can be done in '''Services → Modbus → Modbus TCP Server '''. Once in the Modbus TCP Server configuration, find the '''Enable''' the instance and '''turn on the Allow remote access'''. Everything else can be left as default or changed based on your needs:


==Adding a new slave device==
[[File:Modbus TCP server config new.png|border|class=tlt-border]]
On the master device (in this example master device has 192.168.1.1 internal IP address) open Services->Modbus->Modbus TCP Master. To add a new slave, first, click the add button.


[[File:Picture4.png|frame|center|Modbus Slave configuration on Master device]]


Once you have clicked that button, enter the following configuration so we can add the slave device:


[[File:Picture5.png|frame|center|Modbus Slave Configuration on Master Device Pop Menu]]
Once finished click '''Save & Apply''' to save the configuration.


Scroll down and click “Save and Apply”
==Remote access configuration==
If you wish to remotely access the Modbus TCP Server device navigate to the '''System → Administration → Access Control''' tab. Once in the '''Administration-Access Control''', find the '''Enable remote HTTP access''' field and put a check mark next to it:


[[File:Picture6.png|frame|center|Save and Apply]]
[[File:enable remote access HTTP.png|border|class=tlt-border|]]


After this, this is how your main Modbus Master panel should look:
'''Note:''' If you have a Public IP address already, you can skip this step.


[[File:Picture7.png|frame|center|Modbus Slave Configuration on Master Device]]
To set the APN, while in the router's WebUI, navigate to the '''Network → Mobile → General → Interface mob1s1a1 APN configuration''':


==Testing==
[[File:Set APN PF.png|border|class=tlt-border|alt=]]
For testing, if the functionality is working we can configure a request. A Modbus request is a way of obtaining data from Modbus slaves. The master sends a request to a slave specifying the function code to be performed. The slave then sends the requested data back to the Modbus master. You can create a maximum of 64 request configurations for each slave device.First, click the edit button:


[[File:Picture8.png|frame|center|Modbus Slaves]]
Once in the '''Interface mob1s1a1 APN configuration''' window, edit your mobile interface, find the '''APN''' field and enter you Internet Service Provider's APN:
# '''Disable the Auto APN option'''
# Choose the correct '''APN''', which gives out a public IP address (for more information about that contact your Internet Service Provider)


Scroll down to the “Request configuration” section.  
[[File:Set APN PF APN selected.png|border|class=tlt-border]]


[[File:Picture9.png|frame|center|Request Configuration]]
Additional notes on APN:
* '''NOTE 1''': don't use the exact APN value as seen in the example above as it will not work with your SIM card. APN depends on your Internet Service Provider (ISP), therefore, your ISP should provide you with their APN or, in many case, you can find your ISP's APN with an online search.
* '''NOTE 2''': furthermore, it should be noted that not all SIM cards support this functionality. Static or Dynamic Public IP addresses (obtained through APN) are a paid service and setting any APN value for a SIM card that doesn't support this service will most likely result in losing your data connection. If this is the case, it can be fixed by simply deleting the APN, but it also means that remote access through mobile WAN IP will most likely not work on your SIM card.
* '''NOTE 3''': in some cases the SIM card doesn't require an APN in order to obtain a Public IP address. If that is the case for you, simply check what your router's mobile WAN IP address is - if it's already a Public IP address, then you don't need to set an APN. The easiest way to find what your mobile WAN IP address is to log in to the router's WebUI and check the '''MOB1S1A1''' widget in the '''Overview''' page:


Write a name for the request and click the “Add” button.  
[[File:Where public IP.png|border|class=tlt-border]]


[[File:Picture10.png|frame|center|Add new request]]
=Modbus TCP Client=


And enter a data type, a function, first register, number of registers, if you need brackets or don’t and enable the request. In this case we are trying to get System uptime information so configure the next options:  
==Modbus TCP Client configuration==
On the Modbus TCP Client device open Services → Modbus → Modbus TCP Client. To create a new instance click on '''Add'''. A new pop-up window should appear:


[[File:Picture11.png|frame|center|Configuring Request]]
# '''Enable''' the '''instance'''
# '''Enter''' the '''desired name'''
# '''Server ID''' must match with the previously configured '''Server device ID'''
# Enter the '''mobile WAN IP address of the Modbus TCP Server device'''
# Chose same '''Port as in Server device - 502'''
# Enter '''Period in seconds''', how often requests will be sent to the Server device


Under the “Request Configuration” section there will be another section called “Request Configuration Testing” this is where you can test that the parameters that you set work properly. Just select the request that you want to test and click the test button and you should get and output.
[[File:Enable modbus tcp client config.png|border|class=tlt-border]]


[[File:Picture12.png|frame|center|Testing Configuration]]
==Requesting Modbus data==
For testing, if the functionality is working we can configure a request. A Modbus request is a way of obtaining data from Modbus Server. The Client sends a request to a Server specifying the function code to be performed. The Server then sends the requested data back to the Modbus Client.  


==Alarms==
Scroll down to the '''Request configuration''' section.  Write a name for the request and click the '''Add''' button:
Alarms are a way of setting up automated actions when some Modbus values meet user-specified conditions. To configure these alarms, scroll to the end of the menu and click the “Add” button.


[[File:Picture13.png|frame|center|Alarm Configuration]]
[[File:Add new request modbus tcp client.png|border|class=tlt-border]]


After clicking the “Add” button the next menu should come up:  
In this case we are trying to get System temperature (in 0.1 °C) information so configure the next options:  


[[File:Picture14.png|frame|center|Alarm Configuration Menu]]
# '''Data type''': 32bit INT, Byte order 1,2,3,4 
# '''Function''': Read holding registers (3)
# '''First register''': 6
# '''Number of register'''s: 2
# '''Enble''' brackets if not needed
# '''Enable''' the request
 
The information about correct Modbus registers usage can be found [[https://wiki.teltonika-networks.com/view/Monitoring_via_Modbus_RUTOS|'''here''']].
 
[[File:Add new request modbus tcp test.png|border|class=tlt-border]]
 
Under the '''Request Configuration''' section there will be another section called '''Request Configuration Testing''' this is where you can test that the parameters that you set work properly. Just select the request that you want to test and click the '''test button''' and you should get an output.
 
[[File:Testing modbus TCP client data.png|border|class=tlt-border]]
 
=See Also=
 
Most Teltonika-Networks devices have the Modbus feature. Configuration is described in the user manual Services page for each device.

Latest revision as of 19:47, 13 October 2024

The information on this page is updated in accordance with the 00.07.09 firmware version .

Summary

This article contains instructions on how to configure Modbus TCP functionality on most of the Teltonika Networks devices (with the exception of TAP and TSW series)

Configuration overview & prerequisites

Before we begin, let's take a look at the configuration that we are attempting to achieve and the prerequisites that make it possible.

Configuring port forwarding on Teltonika devices is a simple process that involves just a few steps and can easily be replicated across various devices. The number of devices involved will depend on the specific use case, but the setup can be scaled seamlessly. In the example below, we will use the RUTX50 as the Modbus TCP Client and RUT956 as Modbus TCP Server.

Prerequisites:

  • A device from the RUT, RUTX, RUTM, RUTC or TRB series gateway;
  • A PC, Laptop, tablet or a smartphone
  • Router acting as Modbus TCP Server must have a SIM card with a Public Static or Public Dynamic IP address (more on IP address types here) to make remote access possible
  • (Optional) If the router's SIM card has a Public Dynamic IP address, you may want to additionally configure a Dynamic DNS hostname

If you're having trouble finding this page or some of the parameters described here on your device's WebUI, you should turn on "Advanced WebUI" mode. You can do that by clicking the "Advanced" button, located at the top of the WebUI.

Modbus TCP Server

Configure Modbus TCP Server device. our slave device to have a 192.168.1.2 internal IP address. This can be done by changing the IP address parameter on Network → WAN page:

Modbus TCP Server configuration

Setup router as Modbus TCP Server. It can be done in Services → Modbus → Modbus TCP Server . Once in the Modbus TCP Server configuration, find the Enable the instance and turn on the Allow remote access. Everything else can be left as default or changed based on your needs:


Once finished click Save & Apply to save the configuration.

Remote access configuration

If you wish to remotely access the Modbus TCP Server device navigate to the System → Administration → Access Control tab. Once in the Administration-Access Control, find the Enable remote HTTP access field and put a check mark next to it:

Note: If you have a Public IP address already, you can skip this step.

To set the APN, while in the router's WebUI, navigate to the Network → Mobile → General → Interface mob1s1a1 APN configuration:

Once in the Interface mob1s1a1 APN configuration window, edit your mobile interface, find the APN field and enter you Internet Service Provider's APN:

  1. Disable the Auto APN option
  2. Choose the correct APN, which gives out a public IP address (for more information about that contact your Internet Service Provider)

Additional notes on APN:

  • NOTE 1: don't use the exact APN value as seen in the example above as it will not work with your SIM card. APN depends on your Internet Service Provider (ISP), therefore, your ISP should provide you with their APN or, in many case, you can find your ISP's APN with an online search.
  • NOTE 2: furthermore, it should be noted that not all SIM cards support this functionality. Static or Dynamic Public IP addresses (obtained through APN) are a paid service and setting any APN value for a SIM card that doesn't support this service will most likely result in losing your data connection. If this is the case, it can be fixed by simply deleting the APN, but it also means that remote access through mobile WAN IP will most likely not work on your SIM card.
  • NOTE 3: in some cases the SIM card doesn't require an APN in order to obtain a Public IP address. If that is the case for you, simply check what your router's mobile WAN IP address is - if it's already a Public IP address, then you don't need to set an APN. The easiest way to find what your mobile WAN IP address is to log in to the router's WebUI and check the MOB1S1A1 widget in the Overview page:

Modbus TCP Client

Modbus TCP Client configuration

On the Modbus TCP Client device open Services → Modbus → Modbus TCP Client. To create a new instance click on Add. A new pop-up window should appear:

  1. Enable the instance
  2. Enter the desired name
  3. Server ID must match with the previously configured Server device ID
  4. Enter the mobile WAN IP address of the Modbus TCP Server device
  5. Chose same Port as in Server device - 502
  6. Enter Period in seconds, how often requests will be sent to the Server device

Requesting Modbus data

For testing, if the functionality is working we can configure a request. A Modbus request is a way of obtaining data from Modbus Server. The Client sends a request to a Server specifying the function code to be performed. The Server then sends the requested data back to the Modbus Client.

Scroll down to the Request configuration section. Write a name for the request and click the Add button:

In this case we are trying to get System temperature (in 0.1 °C) information so configure the next options:

  1. Data type: 32bit INT, Byte order 1,2,3,4
  2. Function: Read holding registers (3)
  3. First register: 6
  4. Number of registers: 2
  5. Enble brackets if not needed
  6. Enable the request

The information about correct Modbus registers usage can be found [here].

Under the Request Configuration section there will be another section called Request Configuration Testing this is where you can test that the parameters that you set work properly. Just select the request that you want to test and click the test button and you should get an output.

See Also

Most Teltonika-Networks devices have the Modbus feature. Configuration is described in the user manual Services page for each device.