BACnet is a communication protocol for building automation and control (BAC) networks that use the ASHRAE, ANSI, and ISO 16484-5 standards protocol. It is a additional software that can be installed from the Services → [[RUT955_Package_Manager|Package Manager]] page. | BACnet is a communication protocol for building automation and control (BAC) networks that use the ASHRAE, ANSI, and ISO 16484-5 standards protocol. It is a additional software that can be installed from the Services → [[RUT955_Package_Manager|Package Manager]] page. | ||
=== Configuration === | === BIP Configuration === | ||
---- | ---- | ||
Communications in BACnet over IP (BIP) rely upon the protocol rules of IP and Ethernet. To set up BIP, navigate to Services → BACnet → enable the instance and select BIP port. | |||
=== Server === | === Server === | ||
---- | ---- | ||
For the server, Yet Another BACnet Explorer is used, for data simulation - BACnet Room Control simulator that comes with a server | For the server, Yet Another BACnet Explorer is used, for data simulation - BACnet Room Control simulator that comes with a server | ||
=== MSTP Configuration === | |||
---- | |||
Master - Slave Token Passing (MSTP) is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 128 devices to be installed on a single network. |
Revision as of 09:11, 27 February 2023
The information in this page is updated in accordance with 00.07.03.4 firmware version .
Introduction
This article contains instructions on how to setup BACnet.
Configuration overview and prerequisites
Before we begin, let's take a look at the configuration that we are attempting to achieve and the prerequisites that make it possible.
Prerequisites:
- RUT955;
- Server;
- An end device (PC, Laptop, Tablet, Smartphone) for configuration;
If you're having trouble finding any page or some of the parameters described here on your device's WebUI, you should turn on "Advanced WebUI" mode. You can do that by clicking the "Basic" button under "Mode," which is located at the top-right corner of the WebUI.
BACnet
BACnet is a communication protocol for building automation and control (BAC) networks that use the ASHRAE, ANSI, and ISO 16484-5 standards protocol. It is a additional software that can be installed from the Services → Package Manager page.
BIP Configuration
Communications in BACnet over IP (BIP) rely upon the protocol rules of IP and Ethernet. To set up BIP, navigate to Services → BACnet → enable the instance and select BIP port.
Server
For the server, Yet Another BACnet Explorer is used, for data simulation - BACnet Room Control simulator that comes with a server
MSTP Configuration
Master - Slave Token Passing (MSTP) is most commonly used to connect field devices to controllers / routers / control applications. The physical layer uses RS485 which allows up to 128 devices to be installed on a single network.