Changes

Line 58: Line 58:  
</table>
 
</table>
   −
[[File:Modbus_serial_rut955_1.png|border|class=tlt-border|1100x700px]]
+
----
 +
Now in Modbus Devices section create '''RS232 slave''' by writing a new instance name, selecting rs232 and pressing [[File:Add Button.png|60x90px]] button. In the new window apply the following configuration:
   −
Now create '''RS232 slave''' by writing a name, pressing '''Add''' button. It should appear like in the example and then press '''Edit'''.
+
<table class="nd-othertables_2">
 
+
    <tr>
[[File:Modbus serial rut955 2.png|border|class=tlt-border|1100x700px]]
+
        <th width=330; style="border-bottom: 1px solid white;></th>
 
+
        <th width=800; style="border-bottom: 1px solid white"; rowspan=2>[[File:Modbus Serial RUT955 2.png|border|class=tlt-border|755x406px|right]]</th>
Then apply the following configuration.
+
    </tr>
 
+
    <tr>
[[File:Modbus serial rut955 3.png|border|class=tlt-border|1100x700px]]
+
        <td style="border-bottom: 4px solid white>
 
+
# Check '''Enable''';
[[File:Modbus serial rut955 4.png|border|class=tlt-border|1100x700px]]
+
# Type in desired '''Name''';
 
+
# Type in '''Server ID''' (any number from 1 to 255);
# Check '''Enable'''.
+
# Select '''Period''', e.g. 10;
# Type in desired '''Name'''.
  −
# Type in '''Slave ID''' (any number from 1 to 255).
   
# Write a '''name''' for a new request.
 
# Write a '''name''' for a new request.
# Add new request by clicking '''ADD'''.
+
# Add new request by writing it's name and clicking '''ADD''';
 
# Select '''data type'''.
 
# Select '''data type'''.
 
# Select '''Function''' (Read holding registers (3)).
 
# Select '''Function''' (Read holding registers (3)).
 
# Write '''First register''' (1) and Write '''Register count''' (10).
 
# Write '''First register''' (1) and Write '''Register count''' (10).
 
# Enable the request and you can test it through '''request configuration testing'''.
 
# Enable the request and you can test it through '''request configuration testing'''.
# Press '''Save'''.
+
# Press [[File:Networking save apply button fw76 v1.png|100x35px]] button.
 +
        </td>
 +
    </tr>
 +
</table>
 +
 
 +
[[File:Modbus_Serial_RUT955_3.png|border|class=tlt-border|1050x400px]]
    
==Modbus data to server==
 
==Modbus data to server==