Modbus RTU Master MQTT Serial Gateway

From Teltonika Networks Wiki
Revision as of 09:12, 18 June 2024 by Dziugas.Syminas (talk | contribs) (Reverted edits by PauliusRug (talk) to last revision by Domnev)

(diff) ← Older revision | Approved revision (diff) | Latest revision (diff) | Newer revision → (diff)

The information on this page is updated in accordance with the 00.07.4 firmware version .

Summary

In this guide, the MQTT Serial Gateway function will be configured using third-party MQTT Broker services (in this example, Flespi.io).

Configuration overview & prerequisites

  • Two devices with serials ports - one acts as Modbus RTU Master, another as Modbus RTU Slave;
  • Flespi.io account to act as an MQTT Broker/Publisher/Subscriber (for first configuration example);

RUT2 will act as a Modbus RTU slave and RUT1 as a Modbus RTU Master. On RUT1, MQTT Serial Gateway will be configured to transfer Modbus data over MQTT. Flespi.io platform will serve as an MQTT Broker

RUT2 configuration

Configuring Modbus RTU Slave


Go to Services → Modbus → Modbus RTU Slave and create a new instance.

  • Enter the desired instance name;
  • Select the desired serial interface.
855 × 308px
855 × 308px

RUT1 configuration

Configuring MQTT Gateway


Go to Services → Modbus → MQTT Gateway and there:

  1. Enable the instance;
  2. Enter Host (copied from flespi connection settings without 'wss://' and port);
  3. Enter Username (Copied from flespi Connection settings generated token);
  4. Enter Password.
862 × 412px
862 × 412px

Note: Everything else can be left as default or changed according to your needs.

Configuring Serial Gateway


Under the MQTT Gateway configuration, create the Serial Gateway:

  1. Enter the desired device ID;
  2. Select the desired serial interface.
868×308px
868×308px

Configuring Flespi.io MQTT Broker


Log in or create an account on https://flespi.io;

  1. Navigate to MQTT Board on the left side menu;
  2. On the right-hand panel, top right corner, next to the name of the MQTT board, press the cogwheel-looking icon to open Connection Settings;
  3. In the opened window, press "Get flespi token" to generate a username;
  4. Enter the Client name;
  5. Copy the Host address;
  6. Copy Username;
  7. Create a password.

Once done, save all the changes.

Message format for MQTT publisher


Modbus request data sent in the MQTT payload should be generated in accordance with the following format:

1 <COOKIE> <SERIAL_DEVICE_ID> <TIMEOUT> <SLAVE_ID> <MODBUS_FUNCTION> <FIRST_REGISTER> <REGISTER_COUNT> 

The table below explains what each option means:

1. Format version 1
2. Cookie from 0 to 264 -1
3. Serial device ID a string used to identify a serial device. Must match with Device ID field in MQTT Gateway page Serial gateway configuration section
4. Timeout timeout for Modbus connection, in seconds. Range [1..999].
5. Slave ID Indicates to which slave request is sent
6. Modbus function Modbus task type that will be executed. Possible values are:
  • 1 - read coils;
  • 2 - read input coils;
  • 3 - read holding registers;
  • 4 - read input registers;
  • 5 - set single coil;
  • 6 - write to a single holding register;
  • 15 - set multiple coils;
  • 16 - write to multiple holding registers.
7. First register number (not address) of the first register/coil/input (in range [1..65536]) from which the registers/coils/inputs will be read/written to.
8. Registry count
  • 1 - coil count (in range [1..2000]); must not exceed the boundary (first coil number + coil count <= 65537);
  • 2 - input count (in range [1..2000]); must not exceed the boundary (first input number + input count <= 65537);
  • 3 - holding register count (in range [0..125]); must not exceed the boundary (first register number + holding register count <= 65537);
  • 4 - input register count (in range [0..125]); must not exceed the boundary (first register number + input register count <= 65537);
  • 5 - coil value (in range [0..1]);
  • 6 - holding register value (in range [0..65535]);
  • 15 - coil count (in range [1..1968]); must not exceed the boundary (first coil number + coil count <= 65537); and coil values separated with commas, without spaces (e.g., 1,2,3,654,21,789); there must be exactly as many values as specified (with coil count); each value must be in the range of [0..1].
  • Examples


    Setting relay (on) (Relay address is 202, which means 'Number of first register will be 203) 1 1 1 1 1 6 203 1
    Getting temperature 1 1 1 1 1 3 6 2

    Modbus parameters are held within registers. The register numbers and corresponding system values can be found in this article.

    Testing MQTT Publisher and Subscriber on flespi.io

    Adding Flespi Subscriber


    To test the Modbus Serial Gateway functionality, log into your Flespi accountMQTT Board and add a Subscriber:

    1. Press '+' button on the top right corner
    2. Select 'Subscriber'
    3. In the topic field enter 'response'
    4. Press 'Subscribe' button

    Adding Flespi Subscriber


    Also, you will need to add a Publisher:

    1. Press '+' button on the top right corner
    2. Select 'Publisher'
    3. In the topic field enter 'request'
    4. In the message field enter message, for this example 'Getting temperature' is used
    5. Press 'Publish' button

    Flespi Subscriber output


    Check the response in the 'Subscriber' tab, you should receive a message similar to the one below.



    In the output, we can see that router's temperature is 44 degrees Celsius.

    See Also

    External links

    Flespi.io