RUT955 Modbus

From Teltonika Networks Wiki
Revision as of 11:01, 5 November 2018 by Dziugas (talk | contribs)

Main Page > EOL Products > RUT955 > RUT955 Manual > RUT955 WebUI > RUT955 Services section > RUT955 Modbus

Summary

Template:Webui services modbus summary

Modbus TCP

Template:Webui services modbus modbus tcp

Template:Webui services modbus modbus table

Get Parameters


To obtain parameters from the system, the read holding registers command is used. Router parameters are held within registers. Each register contains 2 bytes of information. For simplification the number of registers for storing numbers is 2, while the number of registers for storing text information is 16. The register numbers and corresponding system values are described below:

REQUIRED VALUE REGISTER NUMBER NUMBER OF REGISTERS REPRESENTATION
System uptime 1 2 32 bit unsigned integer
GSM signal strength (dBm) 3 2 32 bit integer
System temperature in 0.1 degrees Celcius 5 2 32 bit integer
System hostname 7 16 Text
GSM operator name 23 16 Text
Router serial number 39 16 Text
Router MAC address 55 16 Text
Router name 71 16 Text
Current SIM card 87 16 Text
Network registration 103 16 Text
Network type 119 16 Text
Digital input 1 135 2 32 bit integer
Digital input 137 2 32 bit integer
Current WAN IP address 139 2 32 bit unsigned integer
Analog input 141 2 32 bit integer

Set Parameters


The Modbus daemon also supports setting of some system parameters. For this task the Write holding register command is used. System related parameters and how to use them are described below. The register number specifies where to start writing the required values. All commands, except “Change APN”, accepts only one input parameter. For the APN the number of input registers may vary. The very first byte of APN command denotes a number of SIM card for which set the APN. This byte should be set to 1 (in order to change APN for SIM card number 1) or to 2 (in order to change APN for SIM card number 2).

VALUE TO SET REGISTER NUMBER REGISTER VALUE DESCRIPTION
Digital output 1 (ON/OFF) 201 1/0 Changes the state of the Open collector (OC) output (1 -ON; 0 - OFF)
Digital output 2 (ON/OFF) 202 1/0 Changes the state of the Relay output (1 - ON; 0 - OFF)
Switch WiFi (ON/OFF) 210 1/0 Switches WiFi ON or OFF (1 - ON; 0 - OFF)
Switch mobile data connection (on/off) 211 1/0 Switches mobile data connection ON or OFF (1 - ON; 0 - OFF)
Switch SIM card (SIM1, SIM2, SIM1->SIM2 and SIM2->SIM1) 212 0/1/2 Switches SIM card in use
Change APN 213 APN code Changes APN
Reboot 220 1 Reboots the router

See also

You can find more information on how to use Modbus with RUT routers here: Monitoring via Modbus