RUT900 Modbus (legacy WebUI)

From Teltonika Networks Wiki
Main Page > EOL Products > RUT900 > RUT900 Manual > RUT900 Legacy WebUI > RUT900 Services section (legacy) > RUT900 Modbus (legacy WebUI)

The information in this page is updated in accordance with firmware version RUT9XX_R_00.06.09.5.

Note: this user manual page is for RUT900's old WebUI style available in earlier FW versions. Click here for information based on the latest FW version.

Summary

Modbus is a serial communications protocol. Simple and robust, it has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices.

This chapter of the user manual provides an overview of the Modbus page for RUT900 devices.

Modbus TCP

Modbus TCP provides users with the possibility to set or get system parameters. The Modbus daemon acts as slave device. That means it accepts connections from a master (client) and sends out a response or sets some system related parameter in accordance with the given query.

The figure below is an example of the Modbus TCP window section and the table below provides information on the fields contained in that window:

Field Value Description
Enable yes | no; default: none Turns Modbus TCP on or off.
Port integer [0..65535]; default: 502 TCP port used for Modbus communications.
Device ID integer [0..255]; default: 1 The device's Modbus slave ID. When set to 0, it will respond to requests addressed to any ID.
Allow Remote Access yes | no; default: no Allows remote Modbus connections by adding an exception to the device's firewall on the port specified in the field above.
Keep persistent connection yes | no; default: no If enabled, the connection will not be closed after each completed Modbus request.
Connection timeout integer [1..60]; default: 0 Timeout in seconds after which the connection will be closed. Use 0 to use default value provided by Operating System.
Enable custom register block yes | no; default: no Allow custom register block

Get Parameters


Modbus parameters are held within registers. Each register contains 2 bytes of information. For simplification, the number of registers for storing numbers is 2 (4 bytes), while the number of registers for storing text information is 16 (32 bytes). The register numbers and corresponding system values are described in the table below:

required value register number number of registers representation
System uptime 1 2 32 bit unsigned integer
Mobile signal strength (RSSI in dBm) 3 2 32 bit integer
System temperature (in 0.1 °C) 5 2 32 bit integer
System hostname 7 16 Text
GSM operator name 23 16 Text
Router serial number 39 16 Text
LAN MAC address 55 16 Text
Router name 71 16 Text
Currently active SIM card slot 87 16 Text
Network registration info 103 16 Text
Network type 119 16 Text
Current WAN IP address 139 16 32 bit unsigned integer

Set Parameters


The Modbus daemon can also set some device parameters. These parameters and explanations on how to use them are described in the table below:

value to set register address register number register value description
Switch WiFi (ON/OFF*) 210 211 1 | 0 Turns WiFi ON or OFF
Switch mobile data connection (ON/OFF*) 211 212 1 | 0 Turns mobile data connection ON or OFF
Switch SIM card 212 213 1 | 2 | 0 Changes the active SIM card slot
  • 1 - switch to SIM1
  • 2 - switch to SIM2
  • 0 - switch from the the SIM card opposite of the one currently in use (SIM1 → SIM2 or SIM2 → SIM1
Change APN 213 214 APN code Changes APN.
The number of input registers may vary depending on the length of the APN, but the very first byte of the set APN command denotes the number of the SIM card for which to set the APN. This byte should be set to:
  • 1 - to set APN for SIM1
  • 2 - to set APN for SIM2
Reboot 220 221 1 Reboots the router

* All ON/OFF commands only accept 0 and 1 values, which represent the following:

  • 1 - ON
  • 0 - OFF

Modbus TCP Master

A Modbus master device can request data from Modbus slaves. The Modbus TCP Master section is used to configure Modbus TCP slaves. You can create a maximum of 10 slave configurations.

Slave device configuration


The figure below is an example of the Slave device configuration and the table below provides information on the fields contained in that section:

Field Value Description
Enabled yes | no; default: no Turns communication with the slave device on or off.
Name string; default: none Slave device's name, used for easier management purposes.
Slave ID integer [0..255]; default: none Slave ID. Each slave in a network is assigned a unique identifier ranging from 1 to 255. When the master requests data from a slave, the first byte it sends is the Slave ID. When set to 0, the slave will respond to requests addressed to any ID.
IP address ip; default: none Slave device's IP address.
Port integer [0..65535]; default: none Slave device's Modbus TCP port.
Period integer [1..6400]; default: 60 Interval at which requests are sent to the slave device.
Timeout integer [1..30]; default: 5 Maximum response wait time.

Requests configuration


A Modbus request is a way of obtaining data from Modbus slaves. The master sends a request to a slave specifying the function code to be performed. The slave then sends the requested data back to the Modbus master. You can create a maximum of 64 request configurations for each slave device.

Note: Modbus TCP Master uses Register Number instead of Register Address for pointing to a register. For example, to request the Uptime of a device, you must use 2 in the First Register field.

The figure below is an example of the Requests configuration section and the table below provides information contained in the fields of that section:

Field Value Description
Name string; default: Unnamed Parameter Request name. Used for easier management purposes.
Data type Hex | Ascii | 8bit INT | 8bit UINT | 16bit INT, high byte first | 16bit INT, low byte first | 16bit UINT, high byte first | 16bit UINT, low byte first | 32bit float, Byte order 1,2,3,4 | 32bit float, Byte order 4,3,2,1 | 32bit float, Byte order 2,1,4,3 | 32bit float, Byte order 3,4,1,2; default: 16bit INT, high byte first How read data will be stored.
Function 1 | 2 | 3 | 4 | 5 | 6 | 15 | 16; default: 3 A function code specifies the type of register being addressed by a Modbus request. The codes represent these functions:
  • 1 - read Coil Status
  • 2 - read Input Status
  • 3 - read Holding Registers
  • 4 - read Input Registers
  • 5 - force Single Coil
  • 6 - preset Single Register
  • 15 - force Multiple Coils
  • 16 - force Multiple Registers
First Register integer [1..65536]; default: 1 First Modbus register number from which data will be read.
Note - RUT9XX Modbus Master uses register numbers, which value is +1 higher than address value.
Number of Registers integer [1..2000]; default: none Number of Modbus registers that will be read during the request.
Enabled yes | no; default: no Turns the request on or off.
Test - (interactive button) Generates a Modbus request according to given parameters in order to test the request configuration. You must first save the configuration before you can use the Test button.
Delete - (interactive button) Deletes the request.
Add - (interactive button) Adds a new request configuration.

Alarm configuration


Alarms are a way of setting up automated actions when some Modbus values meet user specified conditions. The figure below is an example of the Alarm configuration page and the table below provides information on fields that it contains:

Field Value Description
Enabled yes | no; default: no Turns the alarm on or off
Function code Read Coil Status (1) | Read Input Status (2) | Read Holding Registers (3) | Read Input Registers (4); default: Read Coil Status (1) Modbus function used in Modbus request.
Register integer [0..65535]; default: none Number of the Modbus coil/input/holding register/input register that will be read.
Condition More than | Less than | Equal to | Not Equal to; default: Equal to When a value is obtained it will be compared against the value specified in the following field. The comparison will be made in accordance with the condition specified in this field.
Value various; default: none The value against which the read data will be compared.
Action SMS | Trigger output | Modbus Request; default: SMS Action that will be taken if the condition is met. Possible actions:
  • SMS - sends and SMS message to a specified recipient(s).
  • Trigger output - changes the state of a specified output(s).
  • Modbus Request - sends a Modbus request to a specified slave.
SMS: Message string; default: none SMS message text.
SMS: Phone number phone number; default: none Recipient's phone number.
Trigger output: Output Open collector output | Relay output | Both; default: Open collector output Which output(s) will be triggered.
Trigger output: I/O Action Turn On | Turn Off | Invert; default: Turn On Action that will taken on the specified output.
Modbus Request: IP address ip | host; default: none Modbus slave's IP address.
Modbus Request: Port integer [0..65535]; default: none Modbus slave's port.
Modbus Request: Timeout integer [1..30]; default: 5 Maximum time to wait for a response.
Modbus Request: ID integer [1..255]; default: none Modbus slave ID.
Modbus Request: Modbus function Read Coil Status (1) | Read Input Status (2) | Read Holding Registers (3) | Read Input Registers (4) | Force Single Coil (5) | Preset Single Register (6) | Force Multiple Coils (15) | Force Multiple Registers (16); default: Force Single Coil (5) A function code specifies the type of register being addressed by a Modbus request.
Modbus Request: First register integer [0..65535]; default: none Begins reading from the register specified in this field.
Modbus Request: Number of registers integer [0..65535]; default: none The number of registers that will be read from the first register.


Modbus Data to Server

The Modbus Data to Server function provides you with the possibility to set up senders that transfer data collected from Modbus slaves to remote servers. To add a new data sender, enter the server's address, specify the data sending period and click the "Add" button:

Data sender configuration


When you add a new data sender, you will be redirected to its configuration window. The figure below is an example of that window and the table below provides information on the fields that it contains:

Field Value Description
Enabled yes | no; Default: no Turns the data sender ON or OFF
Name string; Default: none Data sender's name. used for easier management purposes
Protocol HTTP(S) | MQTT; Default: HTTP(S) Data sending protocol
JSON format json string; Default: {"ID":"%i", "TS":"%t","ST":"%s","VR":"%a"} Provides the possibility to fully customize the JSON segment
Segment count 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | All; Default: 1 Max segment count in one JSON string sent to server.
URL / Host / Connection string host | ip; Default: none Address of the server to which the data will be sent.
Important note: when using HTTPS, remember to add the https:// prefix before the URL.
Period integer [1..6400]; Default: none Data sending frequency (in seconds)
HTTP(S): Data filtering All data | By slave ID | By slave IP; Default: All data Which data this sender will transfer to the server
HTTP(S): Retry on fail yes | no; Default: no Specifies whether the data sender should retry failed attempts
HTTP(S): Custom header string; Default: no Adds a custom header(s) to HTTP requests
MQTT: Port integer [0..65535]; Default: none Port used to connect to host.
MQTT: Keepalive integer [1..640]; Default: none MQTT keepalive period in seconds.
MQTT: Topic string; Default: none Write topic to which your data will be sent.
MQTT: QoS 0 | 1 | 2; Default: 0 This field defines the guarantee of delivery for specific message.
Possible values are:
  • At most once (0)
  • At least once (1)
  • Exactly once (2)
  • MQTT: Use TLS yes | no; Default: no Turns TLS authentication on or off.

    MQTT Gateway

    The MQTT Gateway function is used to transfer Modbus data (send requests, receive responses) over MQTT. When it is enabled, the device (this RUT900) subscribes to a REQUEST topic and publishes on a RESPONSE topic on a specified MQTT broker. It translates received MQTT message payload to a Modbus request and relays it to the specified Modbus TCP slave.

    When the MQTT Gateway receives a response from the slave, it translates it to an MQTT message and publishes it on the RESPONSE topic.

    Below is an example of the MQTT Gateway page. Refer to the table for information on MQTT Gateway configuration fields.

    Field Value Description
    Enable off | on; default: off Turns MQTT gateway on or off.
    Host ip | host; default: 127.0.0.1 IP address or hostname of an MQTT broker.
    Port integer [0..65535]; default: 1883 Port number of the MQTT broker.
    Request topic string; default: request MQTT topic for sending requests.
    Response topic string; default: response MQTT topic for subscribing to responses.
    Username string; default: none Username for authentication to the MQTT broker. Leave empty if you do not use client authentication.
    Password string; default: none Password for authentication to the MQTT broker. Leave empty if you do not use client authentication.

    Request messages


    Note: MQTT Gateway uses Register Number instead of Register Address for pointing to a register. For example, to request the Uptime of a device, you must use 2 in the Register Number field.

    Modbus request data sent in the MQTT payload should be generated in accordance with the following format:

    0 <COOKIE> <IP_TYPE> <IP> <PORT> <TIMEOUT> <SLAVE_ID> <MODBUS_FUNCTION> <REGISTER_NUMBER> <REGISTER_COUNT/VALUE>
    

    Explanation:

    • 0 - must be 0, which signifies a textual format (currently the only one implemented).
    • Cookie - a 64-bit unsigned integer in range [0..264]). A cookie is used in order to distinguish which response belongs to which request, each request and the corresponding response contain a matching cookie: a 64-bit unsigned integer.
    • IP type - host IP address type. Possible values:
      • 0 - IPv4 address;
      • 1 - IPv6 address;
      • 2 - hostname that will be resolved to an IP address.
    • IP - IP address of a Modbus TCP slave. IPv6 must be presented in full form (e.g., 2001:0db8:0000:0000:0000:8a2e:0370:7334).
    • Port - port number of the Modbus TCP slave.
    • Timeout - timeoutfor Modbus TCP connection, in seconds. Range [1..999].
    • Slave ID - Modbus TCP slave ID. Range [1..255].
    • Modbus function - Only these are supported at the moment:
      • 3 - read holding registers;
      • 6 - write to a single holding register;
      • 16 - write to multiple holding registers.
    • Register number - number of the first register (in range [1..65536]) from which the registers will be read/written to.
    • Register count/value - this value depends on the Modbus function:
      • 3 - register count (in range [1..125]); must not exceed the boundary (first register number + register count <= 65537);
      • 6 - register value (in range [0..65535]);
      • 16 - register count (in range [1..123]); must not exceed the boundary (first register number + register count <= 65537); and register values separated with commas, without spaces (e.g., 1,2,3,654,21,789); there must be exactly as many values as specified (with register count); each value must be in the range of [0..65535].

    Response messages


    A special response message can take one of the following forms:

    <COOKIE> OK                              - for functions 6 and 16
    <COOKIE> OK <VALUE> <VALUE> <VALUE>...   - for function 3, where <VALUE> <VALUE> <VALUE>... are read register values
    <COOKIE> ERROR: ...                      - for failures, where ... is the error description
    

    Examples


    Below are a few examples of controlling/monitoring the internal Modbus TCP Slave on RUT900.


    Reboot the device

    • Request:
      0 65432 0 192.168.1.1 502 5 1 6 206 1
    • Response:
      65432 OK

    Retrieve uptime

    • Request:
      0 65432 0 192.168.1.1 502 5 1 3 2 2
    • Response:
      65432 OK 0 5590

    If you're using Eclipse Mosquitto (MQTT implementation used on RUT900), Publish/Subscribe commands may look something like this:

    Retrieve uptime

    • Request:
      mosquitto_pub -h 192.168.1.1 -p 1883 -t request -m "0 65432 0 192.168.1.1 502 5 1 3 2 2"
    • Response:
      mosquitto_sub -h 192.168.1.1 -p 1883 -t response
      65432 OK 0 5590


    See also