RUTX09 DLMS

From Teltonika Networks Wiki
Main Page > RUTX Routers > RUTX09 > RUTX09 Manual > RUTX09 WebUI > RUTX09 Services section > RUTX09 DLMS

The information in this page is updated in accordance with firmware version RUTX_R_00.07.06.10.

Summary

The DLMS / COSEM standard suite (IEC 62056 / EN 13757- 1) is the most widely accepted international utility meter data exchange standard. DLMS is the application layer protocol that transforms the data into messages and COSEM describes the general object model and can be used for all kinds of presentations.


This manual page provides an overview of the DLMS functionality in RUTX09 devices.

Note: DLMS is additional software that can be installed from the System → Package Manager page.

Main

The Main page is used to configure DLMS physical devices and Cosem Groups.

DLMS Physical devices


Interoperable devices in DLMS categorize as server (physical device) and client. Data collection device act as a client that supports system dependent features, parameters, functions and classes requesting data from the server (physical device). In this structure, communication protocol stack is independent of application layer so both devices may communicate different media. To add a new physical device, enter an new configuration name and click the 'Add' button.

Networking rutos manual dlms dlms physical devices add button v2.png

After clicking 'Add' you will be redirected to the newly added physical device's configuration page.

DLMS Physical device configuration


The DLMS Physical device configuration section is used to configure the parameters of server (physical device).

Networking rutos manual dlms dlms physical devices configuration v2.png

Field Value Description
Enable off | on; default: off Enables specific physical device configuration.
Connection empty ; default: none DLMS connection.
Name string; default: previously added device name Physical device name.
Server address integer [0..255]; default: 1 DLMS device server address.
Logic server address integer [0..255]; default: 0 DLMS device logical server address.
Client address integer [0..255]; default: 16 DLMS device client address.
Access security none | Low | High | High MD5 | High SHA1 | High GMAC; default: none DLMS device authentication type.
Password string; default: none DLMS device password if authentication is used.
Interface type HDLC | WRAPPER; default: HDLC DLMS device interface type.
Transport security none | Authentication | Encryption | Authentication encryption; default: none DLMS device message encryption.
Invocation counter OBIS code string; default: none DLMS device invocation counter OBIS code.
Authentication key string (Length of the value must be 32); default: none DLMS device authentication key.
Block cipher key string (Length of the value must be 32); default: none DLMS device block cipher key.
Dedicated key string (Length of the value must be 32); default: none DLMS device dedicated key.
Logical name referencing on | off; default: on DLMS devices use Logical Names to reference and access specific data objects or attributes during communication. For example, when requesting data from a device, you might reference a specific Logical Name to retrieve the information.
Test -(interactive button) Test device configuration.

DLMS Cosem groups


To add a new cosem group, enter an new configuration name and click the 'Add' button.

Networking rutos manual dlms dlms cosem groups add button.png

After clicking 'Add' you will be redirected to the newly added cosem group's configuration page.

DLMS Cosem group configuration


The DLMS Cosem group configuration section is used to configure the parameters of cosem groups.

Networking rutos manual dlms dlms cosem groups configuration v2.png

Field Value Description
Enable off | on; default: off Enables Cosem group.
Name string; default: previously added cosem group name OBIS code group name.
Interval integer [1..4294967295]; default: 1 Interval for OBIS code reading (in seconds).
Test -(interactive button) Test cosem group.

DLMS Cosem value


Cosem value is a specific value retrieved from a defined server (physical device). To add a new cosem value, enter an new configuration name and click the 'Add' button.

Networking rutos manual dlms dlms cosem value add button v2.png

After clicking 'Add' you will be redirected to the newly added cosem value's configuration page.

Networking rutos manual dlms dlms cosem value configuration.png

Field Value Description
Enable off | on; default: off Enables Cosem state.
Name string; default: previously added cosem value name COSEM option name.
Physical device selection; default: none Physical device to read from.
OBIS code string; default: none OBIS code value, actions are not executed, only properties are read.
COSEM class id DATA (ID: 1) | REGISTER (ID: 3) | REGISTER (ID: 3) | DEMAND REGISTER (ID: 5) | REGISTER ACTIVATION (ID: 6) | PROFILE GENERIC (ID: 7) | CLOCK (ID: 8) | SCRIPT TABLE (ID: 9); default: DATA (ID: 1) Object type for OBIS code.
Entries interger [1..32767]; default: none How many data objects to read.

Connections

The Connections page is used to configure DLMS connections. You can use either TCP or serial (depending on the router) connection to establish a connection between the physical device and the router.

DLMS Connections


To add a new connection, enter an new connection name and click the 'Add' button.

Networking rutos manual dlms dlms connections add button.png

After clicking 'Add' you will be redirected to the newly added connection's configuration page.

DLMS Connection configuration


The DLMS Connection configuration section is used to configure the parameters of connections.

Networking rutos manual dlms dlms connections configuration.png

Field Value Description
Enable off | on; default: off Enables Cosem state.
Name string; default: previously added connection name Name of DLMS connection configuration.
Connection type TCP | Serial; default: TCP DLMS connection type.
Serial device USB RS232 interface; default: USB RS232 interface DLMS serial device.
Baud rate 300 | 1200 | 2400 | 4800 | 9600 | 19200 | 38400 | 57600 | 115200; default: 9600 Serial data transmission rate (in bits per second).
Data bits 5 | 6 | 7 |8; default: 8 Number of data bits for each character.
Stop bits 1| 2; default: 1 Stop bits sent at the end of every character allow the receiving signal hardware to detect the end of a character and to resynchronise with the character stream. Electronic devices usually use one stop bit. Two stop bits are required if slow electromechanical devices are used.
Parity Even | Odd| Mark | Space | None; default: None In serial transmission, parity is a method of detecting errors. An extra data bit is sent with each data character, arranged so that the number of 1 bits in each character, including the parity bit, is always odd or always even. If a byte is received with the wrong number of 1s, then it must have been corrupted. However, an even number of errors can pass the parity check.
  • None (N) - no parity method is used.
  • Odd (O) - the parity bit is set so that the number of "logical ones (1s)" has to be odd.
  • Even (E) - the parity bit is set so that the number of "logical ones (1s)" has to be even.
  • Space (s) - the parity bit will always be a binary 0.
  • Mark (M) - the parity bit will always be a binary 1.
Flow control None | RTS/CTS | Xon/Xoff; default: None In many circumstances a transmitter might be able to send data faster than the receiver is able to process it. To cope with this, serial lines often incorporate a "handshaking" method, usually distinguished between hardware and software handshaking.
  • RTS/CTS - hardware handshaking. RTS and CTS are turned OFF and ON from alternate ends to control data flow, for instance when a buffer is almost full.
  • Xon/Xoff - software handshaking. The Xon and Xoff characters are sent by the receiver to the sender to control when the sender will send data, i.e., these characters go in the opposite direction to the data being sent. The circuit starts in the "sending allowed" state. When the receiver's buffers approach capacity, the receiver sends the Xoff character to tell the sender to stop sending data. Later, after the receiver has emptied its buffers, it sends an Xon character to tell the sender to resume transmission.
IP address ip; default: none DLMS device IP address for TCP connection.
Port integer [1..65535]; default: none DLMS device IP port for TCP connection.